background image

N200-102-00

3

I56-3947-200

Figure 7: Sequence (1 to 9) to Mount the Detector on the Bracket

Pipe Installation

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1

7 18

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

18

99 mm

41

1

2

mm

90 mm

4

3

0.00

o

5

329 mm

6

7

7a

7b

7c

7d

8

9

1

2

FAAST LT MODEL 

INLET PIPE HOLE

OUTLET PIPE HOLE

NFXI‐ASD11 

1 & 2, or 1 or 2 

NFXI‐ASD12 

1 & 2, or 1 or 2 

NFXI‐ASD22 

Channel 1 ‐ 1 & 2, or 1 or 2 

Channel 2 – 3 & 4, or 3 or 4 

 

Pipe Hole Configuration

Figure 8

 below shows the pipe holes available on the unit. Each 

unit has 2 pipe holes per channel (so if installing a 1 channel unit, 

holes 3 and 4 do not function). Use 

Table 1

 to locate the holes 

required for the installation:

Figure 8: Pipe Holes

Table 1: Pipe Holes Used for Each FAAST LT Model

Note 1:

 Pipe holes not used should be kept sealed.

Note 2:

 Do 

NOT

 glue pipes into the pipe holes.

Table 1a: Maximum Number of Pipe Holes Allowed Per Channel  

for EN54-20 Compliance

All figures quoted using highest (level 1) sensitivity.

1

2

3

4

5

6

CLASS

 

PIPE

 

LENGTH

 

(m)

 

MAX

 

NUMBER

 

OF

 

HOLES

 

PER

 

CHANNEL

 

C

 

100 

18 (10 x 2.5mm, 8 x 3mm) + 3mm 

non sensing end hole) 

B

 

100 

6 (4 x 4mm, 2 x 5mm inc end hole)

A

 

80 

3 (1 x 5mm, 2 x 6mm inc end hole) 

 

Summary of Contents for Notifier FAAST LT NFXI-ASD Series

Page 1: ...tor Characteristics Maximum rated switching current under short circuit Is max 0 9A 29V Maximum leakage current IL max with the switch open isolated state 15mA Maximum series impedance with the switch closed Zc max 190 m ohm at 15Vdc 1A Power Reset 0 5s Configurable Input Activation Time 2s min Relay Contact Ratings 2 0 A 30 VDC 0 5A 30 VAC Environmental Ratings Temperature 10 C to 55 C Relative H...

Page 2: ... labels fixed in place This allows the installer to choose the language required for the installation from the Front Panel Labelling Pack Figure 2 shows where the labels need to be placed 1 2 3 Figure 6 Fasten the mounting bracket to the wall Mounting the LT NFXI ASD to the Wall Figure 2 Placing the Front Panel Labels 2 10 3 1 4 5 6 7 8 9 2 10 3 1 4 5 6 7 8 9 IN PU T SE NS OR ASPI RATO R E L B A S...

Page 3: ...e unit Each unit has 2 pipe holes per channel so if installing a 1 channel unit holes 3 and 4 do not function Use Table 1 to locate the holes required for the installation Figure 8 Pipe Holes Table 1 Pipe Holes Used for Each FAAST LT Model Note 1 Pipe holes not used should be kept sealed Note 2 Do NOT glue pipes into the pipe holes Table 1a Maximum Number of Pipe Holes Allowed Per Channel for EN54...

Page 4: ...ANNEL 2 FILTER POWER AND ALARM CONNECTIONS CHANNEL 1 FILTER USB PORT SENSOR COVER POSITION FOR TEST MAGNET POSITION FOR TEST MAGNET Exhaust Pipe SAMPLING AREA SAMPLING AREA 5 6 EARTH BAR MOUNT EARTH BAR MOUNT EARTH BAR OPTIONAL Note 1 All wiring should comply with local requirements and regulations Note 2 Loop wiring must observe the recommendations of the panel manufacturer 3 4 ...

Page 5: ...hen smoke is detected by one of the Aspirated Smoke Detector units but not the other To avoid problems ensure that no VIEW sensors on a loop have addresses set adjacent to the address values set in an Aspirating Smoke Detector POWERING UP Using Default Settings 1 Connect a suitable 24VDC supply complying with European Standard EN 54 4 to pins 1 and 2 on terminal block T1 See Table 2 Table 3 Relays...

Page 6: ...E R F IL T E R L O W F L O W H IG H F L O W E L B A S I D M E T S Y S 2 10 3 1 4 5 6 7 8 9 MODULE 1 LEVEL 1 SMOKE FAULT FAULT POWER LEVEL 2 SMOKE MODULE 2 ALARM PREALARM IN P U T S E N S O R AS PI RA TO R E L B A S I D M E S Y TE MP ER AT UR E S O U N D E R F IL T E R L O W F L O W H IG H F L O W S T 2 10 3 1 4 5 6 7 8 9 2 10 3 1 4 5 6 7 8 9 2 Check the voltage at the connector Make sure it is wit...

Page 7: ...w when initialising POWER FAULT ON Yellow Low power alert high power fault Check the power supply voltage CHANNEL FLOW INDICATORS 1 2 ON Green The LED indicates the air flow for a channel Centre normal flow Left flow low 20 at extreme Right flow high 20 at extreme On 2 channel unit Upper row Ch1 Lower row Ch2 LOW FLOW ON Low flow fault Check filter check pipe network for blockages INPUT 1 BLINK Ex...

Page 8: ...e Mode Opening the cabinet door during normal operation will cause the unit to enter Service Mode The FILTER LEDs will blink the unit will switch off power to the fans and stops communicating with the fire panel the smoke sensors continue to communicate with the panel When the cabinet door is closed the unit restarts automatically Filters Periodic cleaning or replacement of the filters will be req...

Page 9: ...ng normal operation 1 2 3 PipeIQ LT QUICK START INSTRUCTIONS Overview of PipeIQLT The PipeIQLT software program is a convenient and powerful Windows based application that can be used to quickly and accuratelydesignpipenetworks generateconfigurationparameters for correct set up and operation and facilitate commissioning and monitoring of the performance of FAAST LT Aspiration devices PipeIQLT prov...

Page 10: ...uter in the normal way for your operating system Launching To launch the PipeIQLT application double click the PipeIQLT icon on the desktop Or click Start bottom left corner of the Windows screen and then select PipeIQLT from the programs list When the application opens it is possible to start a new project or to monitor or modify an existing project Use the File menu to select New or Open Choose ...

Reviews: