39
DCV OVP Fault
DC component is out of limit in output voltage.
·
Disconnect PV, grid, and battery, then reconnect
·
Or seek help from us, if not go back to normal state
SW OCP Fault
Output current high detected by software
·
Disconnect PV, grid, and battery, then reconnect
·
Or seek help from us, if not go back to normal state.
RC OCP Fault
The residual current is high.
·
Please check if the insulation of electric wires is damaged.
·
Wait for a while to check if back to normal.
·
Or seek for help from us.
Iso Check Fault
The isolation is failed.
·
Please check if the insulation of electric wires is damaged Wait for a
while to check if back to normal.
·
Or seek for help from us.
Temp Over Fault
The inverter temperature is high.
·
Please check if the environment temperature.
·
Wait for a while to check if back to normal.
·
Or seek for help from us.
BatConDir Fault
The battery connection is reversed.
·
Check if the positive pole and negative pole of battery are correctly
connected
·
Or seek help from us.
AD Sample Fault
The sample value between master and slave is not consistent.
·
Disconnect PV, grid, and battery, then reconnect.
·
Or seek help from us, if not go back to normal state.
EPS Over Load
Over load in off grid mode.
·
Please check if the eps load power exceeds the limit
·
Or seek for help from us.
Over Load Fault
Over load in on grid mode
·
Please check if the load power exceeds the limit.
·
Or seek for help from us.
Summary of Contents for BRE-I-5K
Page 1: ...1 User Manual BRE I 5K OLIPOWER ENERGY AUTOMATION TECHNOLOGY...
Page 28: ...28 1 ADD Interface ADD interface PINS definition...
Page 33: ...33...
Page 34: ...34...
Page 54: ...54 Reactive power setting After user log into the system Remote control Reactive power...
Page 55: ...55 Volt watt setting After user log into the system Remote control Australia...
Page 62: ...62...