27
Figure 5-9 EPS cable installation
5.7.4
Earth connection
You can additionally earth the inverter enclosure of a second earthling or
equipotential bonding is required locally. This prevents touch current if the
original protective conductor fails.
Cable size:12AWG
Connection step
:
·
Strip the earthling cable insulation.
·
Insert the stripped cable into the ring terminal.
·
Clamp the end of the ring terminal.
·
Unscrew the screw of the earthling connector.
·
Suit the ring terminal on the earthling connector.
Suit the gasket on the earthling connector.
·
Screw the screw of the earthling connector.
5.7.5
Communication connection
Communication interface
This product has a series communication interface
besides Dry contact and extend port and for human and machine
communication, etc., can be delivered to PC or other monitoring equipment via
these interfaces.