Page 56
8.2.
Installation of WinPro / MX62
ATTENTION!
Make sure power supply is cut off prior opening the unit.
8.2.1.
Wall-mounted housing
The size of the wall-mounted housing depends on the number of modules.
Safety systems should always be installed at a distance from any devices
with high generic emission.
Attention is to be paid to free accessibility.
8.2.2.
19 inch rack
The distance between the 19 inch rack and the mounting plate must be
less than three meters.
The sheath of the shielded line should be connected with the housing at
the entry of the switchboard cabinet and on the mounting plate.
The relay modules and LED modules can be connected by a flat or bus
cable. The maximum bus length is 800 m.
8.2.3.
Control panel
The distance between CM and mounting plate must be less than three
meters.
The sheath of the shielded line must be connected with the housing on the
mounting plate.
The relay modules and LED modules can be connected by a flat or bus
cable. The maximum bus length is 800 m.