Page 22
3.3.1.
Operating status
The measured signal is within the measuring range and the preset alarm
levels.
Display, messages, outputs:
LED module:
LED
Power
is on
System:
all LED are off, no relay is activated
RBM/REM:
no relay is activated
AAM:
4-20 mA or 0-10 V
(corresponding to the detected gas concentration)
LCD module:
normal operation (see chapter 4)
Printer:
no message
3.3.2.
Alarms
The system WinPro
®
/ MX62 has three free adjustable alarm levels within
the measuring range of 4-20 mA.
The software
ConfigPro
allows, for example, adjusting of alarm levels,
latching of alarms or setting of alarm thresholds for mean values within a
specified time. Furthermore, alarms can be triggered in case of over or
under run of alarm levels.
For numerous target gases, preset measuring profiles are available in
ConfigPro
.
Display, messages, outputs:
LED module:
corresponding LED
Alarm
are on
System:
all LED are off, no relay is activated
RBM/REM:
corresponding relays
Alarm 1
,
Alarm 2
and/or
Alarm 3
are activated
AAM:
4-20 mA or 0-10 V
(corresponding to the detected gas concentration)
LCD module:
message:
Alarm 1
,
Alarm 2
and/or
Alarm 3
Printer:
message:
Al1
,
Al2
and/or
Al3
3.3.3.
Channel fault
In case of channel malfunction, the measured signal has either fallen
below 2 mA or exceeded 24.5 mA. Channel malfunction could, for
example, mean interruption or short circuit of the signaling line. The
detector may also be defective.
It is also possible that communication with AEM or LOOPM is
interrupted. In this case, all channels go into the fault mode about 30
seconds following loss of communication.
Summary of Contents for MX62
Page 2: ...Subject to change without notice FE BA WinPro MX 62 R6 GB 1604CBR...
Page 4: ...Page 4...
Page 10: ...Page 10...
Page 18: ...Page 18...
Page 58: ...Page 58...
Page 60: ...Page 60...
Page 64: ...Page 64...
Page 65: ...Page 65 12 EU declaration of conformity...
Page 66: ...Page 66...
Page 68: ...Page 68...