Page 46
4 system relays (on CM)
Signal outputs
4-20 mA or 0-10 v (by AAM); load for
- 4-20 mA
: maximum 450 Ω
- 0-10 V
: minimum 100 kΩ
signal accuracy: < 2,5% upper range value
Datalogger
64 Mbit storage card (on CM)
Digital interfaces
- RS485, for communication with digital detectors (on
AEM / LOOPM)
- RS232, for configuration and visualization or
calibration of digital detectors (on CM)
- Centronics printer port
Certification:
ATEX (Directive 94/9/EC)
0158
II (2)G, BVS 03 ATEX G 002 X
Performance approval for explosion protection:
- for combustible gases: according EN 60079-29-1
- for oxygen (inertisation): according EN 50104
Performance approval for oxygen
according EN 50104, PFG-Nr. 41300402
(Detection of oxygen deficiency and enrichment)
Performance approval for toxic gases
according EN 45544-1 / -2, PFG-Nr. 41300402
EMC (Directive 2004/108/EC)
according EN 50270 (type 1 and type 2)
Low Voltage (Directive 2006/95/EC)
according EN 61010-1
Functional Safety
SIL2 / SIL3 capable, according EN 61508 / EN 50402
Please see relevant data sheets for technical details of respective detectors.