Page 31
Display, messages, outputs:
LED module:
as operation status or all LED
Fault
are flashing
System:
LED
Single Mode
flashes, the relay
Single mode
is activated
RBM/REM:
as operation status
AAM:
as operation status
LCD module:
message:
Single mode
or display failure
Printer:
message:
Emergency operation relay activated
3.6.
System failure
In this case, the safety function has failed (see chapter 3.7). Two separate errors
have occurred in the WinPro
®
/ MX62.
The system failure is only indicated after the system has tried to maintain the
measuring function by resetting. During this time, the system operates as if it is
in start-up mode though the outputs of the relay modules are not reset.
Depending on the configuration of the system, there can be a time delay of up to
90 s between error occurrence and indication.
ATTENTION!
The gas detection system WinPro
®
/ MX62 differentiates the faults of the
complete system from those of a specific channel (chapter 3.3.3).
When configuring safety control devices to be connected to the system, please
bear in mind that a system error does not automatically lead to activation of all
relay outputs for channel malfunctions. In this case, the switch position of the
relay
System failure
has to be taken in account.
Display, messages, outputs:
LED module:
all LED
Fault
are on
System:
LED
System failure
is on, the relay
System failure
is activated
RBM/REM:
status at begin of system failure will remain
AAM:
0 mA or 0 V
LCD module:
message:
System failure
or display failure
Printer:
message:
Failure relay activated
or printer failure
Summary of Contents for MX62
Page 2: ...Subject to change without notice FE BA WinPro MX 62 R6 GB 1604CBR...
Page 4: ...Page 4...
Page 10: ...Page 10...
Page 18: ...Page 18...
Page 58: ...Page 58...
Page 60: ...Page 60...
Page 64: ...Page 64...
Page 65: ...Page 65 12 EU declaration of conformity...
Page 66: ...Page 66...
Page 68: ...Page 68...