Page 47
7.
Connection and configuration of the modules
7.1.
Controller module (CM)
The CM, consisting of two PCBs, is fitted with relays for indication of service
mode (make contact), single mode (make contact) as well as system failure
(break contact). The relays are only provided for signals of up to 30 V DC, 0.1
A.
The rotary switch allows setting of the various functions for servicing (see
chapter 3.4).
At the
External Reset
input all relevant relays and latching alarms can be reset
with an external key connected.
In case no emergency power is supplied (24 V), a bridge connection between the
24 V inputs has to be made.
Single M.
External Reset
LED
µCA
Error
LED
µCB
Error
LED
Service
Output Module
LED
Display of
Rotary Switch
with basic PCB
and additional
plugged PCB
RS-232 (PC)
Centronics(printer)
Display
Reset
Controller Module
µC B
Status
µC B
Analog Input Modules
Display
Rotary Switch
for Servicing
Output
A
Output
B
Mode
System-
failure
Service
Single
µC A
EPS Signal or +24 V
+24V
GND
Reset
Status
µC A