Buffer sensor (TPO, TPM)
Two buffer sensors are required in the buffer tank.
The heat pump is switched on based on readings
from the TPO and switched off based on those
from the TPM.
-
Install a sensor pocket in the female socket
provided for the upper buffer sensor (TPO)
-
Install a sensor pocket in the female socket
provided for the lower buffer sensor (TPM)
NOTE
In systems with
direct heating circuit,
install the TPO sensor in the heating
flow of the heat pump indoor unit.
-
Install the TPO sensor in the indoor
unit at the marked location on the
heating flow pipe, downstream
from the electric booster heater
(MFA).
-
The required controller parameters
are set by OCHSNER customer
service or specialist personnel
authorised by OCHSNER.
In systems with a buffer tank, a bypass
or a low loss header or a heating
circuit with mixing valve, the TPO
sensor must
not be installed in the
indoor unit
.
Figure 69: Pipe marking in the heat pump indoor unit
Summary of Contents for AIR BASIC 109
Page 2: ...BA_AIR_BASIC_ELW_Multitower_OTE3_SW5x_CC_EN_V08 docx Page 2 of 92...
Page 22: ...BA_AIR_BASIC_ELW_Multitower_OTE3_SW5x_CC_EN_V08 docx Page 22 of 92...
Page 79: ...BA_AIR_BASIC_ELW_Multitower_OTE3_SW5x_CC_EN_V08 docx Page 79 of 92...
Page 80: ...BA_AIR_BASIC_ELW_Multitower_OTE3_SW5x_CC_EN_V08 docx Page 80 of 92...
Page 81: ...BA_AIR_BASIC_ELW_Multitower_OTE3_SW5x_CC_EN_V08 docx Page 81 of 92...
Page 82: ...BA_AIR_BASIC_ELW_Multitower_OTE3_SW5x_CC_EN_V08 docx Page 82 of 92 11 5 ERP Data...
Page 83: ...BA_AIR_BASIC_ELW_Multitower_OTE3_SW5x_CC_EN_V08 docx Page 83 of 92...
Page 84: ...BA_AIR_BASIC_ELW_Multitower_OTE3_SW5x_CC_EN_V08 docx Page 84 of 92...
Page 85: ...BA_AIR_BASIC_ELW_Multitower_OTE3_SW5x_CC_EN_V08 docx Page 85 of 92...
Page 86: ...BA_AIR_BASIC_ELW_Multitower_OTE3_SW5x_CC_EN_V08 docx Page 86 of 92...
Page 87: ...BA_AIR_BASIC_ELW_Multitower_OTE3_SW5x_CC_EN_V08 docx Page 87 of 92...
Page 90: ...BA_AIR_BASIC_ELW_Multitower_OTE3_SW5x_CC_EN_V08 docx Page 90 of 92...
Page 91: ...BA_AIR_BASIC_ELW_Multitower_OTE3_SW5x_CC_EN_V08 docx Page 91 of 92...