![OBO Bettermann isCon BA 45 SW System Instructions Download Page 57](http://html1.mh-extra.com/html/obo-bettermann/iscon-ba-45-sw/iscon-ba-45-sw_system-instructions_722016057.webp)
System instructions OBO isCon
®
EN | 57
Installing the isCon® system
Routing on non-conductive building structures
When routed along a non-conductive building structure (e.g. stone, con-
crete or wood):
• Route electrically conductive connection rails (e.g. flat conductor, type
5052 V2A 30x3.5) in parallel to the isCon
®
conductor, which you con-
nect with the functional equipotential bonding of the building.
• Fasten the metallic isCon
®
H VA cable bracket for the isCon
®
conduc-
tor to it.
≤ 500 mm
isCon H VA
Figure 62:
isCon
®
conductor in potentially explosive area with isCon
®
H VA cable
bracket mounted on flat conductor
Routing along metallic pipes
• Connect the potential connection element to metal pipes routed in
parallel (equipotential bonding conductors) and connected to the build-
ing's equipotential bonding at regular intervals.
≤ 500 mm
isCon HS VA
Figure 63:
Running the isCon
®
conductor on an earthed pipe in a potentially
explosive area