Installing the isCon® system
5 4
Fastening the air-termination rod to pipes, a wall or T
support
The isCon
®
system can offer supports for fastening to pipes, walls or
T supports for mounting isFang air-termination rods with air-termination
rod stands (see “„3.4.2 Air-termination rod support for isFang mounting“
on page 17). This applies to air-termination rods with openings at the
side or the bottom, as well as to rods with an external isCon
®
conductor.
Figure 52:
Fastening air-termination rods to pipes, walls or T supports
Please note:
– Fasten the air-termination rod to the building structure using the sup-
ports listed in Table 6 on page 17 and suitable fastening materials.
– In the case of a non-metallic building structure, connect the equipoten-
tial bonding directly to the equipotential bonding of the air-termination
rod (see “„5.6 Attaching the potential connection“ on page 49).
Note!
In the case of a metallic, earthed building structure, the equipotential
bonding is created using the metallic fastening clips of the air-termination
rod. No additional connection is required.