Arcnet Baud rate
The standard baud rate of the Arcnet network is
156KBaud. For diagnosis purpose under use of
special hardware the baud rate can be set to
2,5MBaud.
Since software version S040A12.05 the baud
rate setting will be stored permanently in
flash memory.
88
Sections
1. Arcnet
2. RS485 device
Cancel Enter
Sections
Sections can be defined for networked panels and for
devices communicating by "FRP protocol", i.e. LCD
repeater panel
Network sections
-> menu
89
FRP protocol sections
-> menu
90
89
Sections 0001/1000
Network-ID 001 Zon. 0001 – Zon. 0010
↓
+1
↑
-1 Selection ->+10 <--10
>0001: No. 001 Zon.0001 – Zon.0010
0002: No. 002 Zon.0038 – Zon.0040
0003: No. 003 Zon.0400 – Zon.0499
Cancel +100 -100 save
Network sections
To limit the display of messages and the control
possibilities on a certain panel in a network, a
maximum of 1000 sections can be configured.
In the left hand example 3 sections for 3 different
network IDs have been programmed.
As soon as any section has been defined for a certain
network ID, all common messages, i.e. "Power supply
fault", from this ID will automatically be displayed
additionally to messages of the configured zones.
90
Sections 0001/1000
RS485 device 1
Network-ID 001 Zon. 0001 – Zon. 0010
↓
+1
↑
-1 Selection ->+10 <--10
>0001:Addr 01 No.001 Zon.0001 – Zon.0010
0002:Addr 02 No.001 Zon.0011 – Zon.0040
0003:Addr 03 No.001 Zon.0041 – Zon.0099
Cancel +100 -100 save
FRP protocol sections
After having selected a device out of the list of a
maximum of 63 devices a maximum of 1000 sections
can be defined to limit the display of messages, i.e.
on a LCD repeater panel.
In the left hand example 3 sections for 3 different
"FRP protocol" devices have been programmed.
On the first device, i.e. a LCD repeater panel, only
messages from zone 1 to zone 10 will be displayed,
on the second device only messages from zone 11 to
zone 40 and on the third device messages form zone
41 to 99.
As soon as any section has been defined for a certain
"FRP protocol" device, all common messages, i.e.
"Power supply fault", from this ID will automatically be
displayed additionally to messages of the configured
zones.
91
Webserver
IP-Address
: 192.168.0.127
Netmask
: 255.255.255.0
Network
: 192.168.0.0
Gateway
: 192.168.0.254
Cancel "." UserInit save
Webserver Settings
The webserver settings generally should be done by
the configuration software.
Nevertheless the settings also can be changed at the
control panel directly.
If the webserver module has been recognized by tge
FCP the first time, the basic configuration has to be
made by the function "Delete program". Alternatively
the settings can be initialized by loading a