NSC Sicherheitstechnik GmbH
47/69
14.08.2013
Lange Wand 3
B01050 B01060 Operating Installation Manual Solution F1 20130814.doc
33719 Bielefeld
Version S040A13.08
The functions are disabled by F2 ("No") and the
functions are enabled by F3 ("Yes").
After setting the parameters please press F4
("Enter") to save the configuration.
105
Functions for outputs
Function Output 001
Sounder/Strobe activation : No
Tansm.Dev. activat. permanent : No
Tansm.Dev. activat. impulse : No
Saved Reply Message : No
Reset FCP : No
KDB output active : No
↓
Cancel No Yes save
Function Output 001
Buzzer : No
↑
Cancel No Yes save
Functions for inputs
Function Input 001
Fire outputs : No
Sounder : No
Alarm Transm.Dev. : No
Delay : No
Buzzer off : No
FCP Reset : No
Cancel No Yes save
Functions for Push button S_ 001
Function Special Key 001
Fire outputs : No
Sounder : No
Alarm Transm.Dev. : No
Delay : No
Cancel No Yes save
Automatic Control: Functions
Here the user can assign certain fixed functions to the
inputs/outputs or special keys. For example he can
assign the "sounder/strobe activation” to an output
and in that case this output is activated and
deactivated at the same time as the external
sounders/strobes.
If one of these functions is used it is not possible
to assign any other cause and effect events to the
same output.
The sense is to create a parallel output to the listed
outputs on the left side.
The function "Saved Reply Message” is a special
function of the German Alarm Transmission Device.
This device sends back a signal to the panel if the
Fire Brigade is alarmed. This signal is acknowledged
by the FCP and if this parameter is set to "yes” the
relating output indicates this feed back signal by
activation.
The functions are disabled by F2 ("No") and the
functions are enabled by F3 ("Yes").
After setting the parameters please press F4
("Enter") to save the configuration.
106
Autom.controlling Output 001
all events
Events for selection
Cancel Enter
Selection of displaying cause and effect
events
A cause and effect event is a link / configuration of
inputs and outputs combined with logical AND or OR.
Cause and effect events are possible at the FCP
"Solution F1" for OC outputs, relays, power outputs,
output modules, inputs, input modules und macro
push buttons.
The user can choose if he wants to see all events in
the LC module or just the events relating to the output
he is configuring at the moment :
"All Events" means all 2048 possible events will be
displayed.
"Events for selection" means only the cause and
effect events of the selected input / output / push
button will be displayed.