NSC Sicherheitstechnik GmbH
51/69
14.08.2013
Lange Wand 3
B01050 B01060 Operating Installation Manual Solution F1 20130814.doc
33719 Bielefeld
Version S040A13.08
Table of multi sensor ACA-E sensitivities and
modes:
Sens.
Mode 1 /2
Opt./ Multi
Mode 3
Heat
Mode 4
Heat+Opt.
1
2,0 %
50°
60°+2,0%
2
2,5 %
55 °
78°+2,0%
3
3,0 % EN54
60° - A1S
60°+3,0%
4
3,5 %
66°
78°+3,0%
5
4,0 %
72°
60°+4,0%
6
4,5 %
78° - BS
78°+4,0%
7
-
83°
88°+2,5%
8
-
88° - CS
88°+3,5%
Table of multi sensor ACB-E modes:
Modus
Meaning
1
Maximum Detector
2
Max.-Diff Detector
Table of multi sensor ACB-E sensitivities and
modes:
Sens.
Modus 1
Fix.
Modus 2
Fix. + Rate of rise
1
50°
60 °C - A1R + 14 K/min
2
55 °
60 °C - A1 + 25 K/min
3
60° - A1S
78 °C – BR +16 K/min
4
66°
78 °C – B +25 K/min
5
72°
88 °C – CR + 16 K/min
6
78° - BS
88 °C – C + 25 K/min
7
83°
-
8
88° - CS
-
Only for Apollo
Table for detector sensitivities:
Ionisation smoke detector Discovery
Sens.
Alarm
threshold
Minimum time to
alarm
1
0,45
5 Sec.
2
0,45
30 Sec.
3
0,70
5 Sec.
4
0,70
30 Sec.
5
1,0
5 Sec.
Optical smoke detector Discovery
Sens.
Alarm
threshold
Minimum time to
alarm
1
1,4
5 Sec.
2
1,4
30 Sec.
3
2,1
5 Sec.
4
2,1
30 Sec.
5
2,8
5 Sec.
Only for Apollo
one of 5 sensitivities during the day (see
table in left column)
one of 5 sensitivities during the night (see
table in left column)
the mode has no meaning and will be
automatically set by the sensitivities (see
table in left column).