NSC Sicherheitstechnik GmbH
40/69
14.08.2013
Lange Wand 3
B01050 B01060 Operating Installation Manual Solution F1 20130814.doc
33719 Bielefeld
Version S040A13.08
After selecting a push button an access code can be
specified by pressing F2 ("settings") -> Sprung in
Menu
117
Press F3 ("Function")
Jump to Menu
105
(selection of standard function for this push button)
75
Installer
old access code: 00000
new access code: 22351
new access code: 22351
Cancel
Changing the installer access code
First you have to type the old access code, and then
you have to type two times the new access code.
Every line has to be confirmed with "OK".
Example left side: old access code 00000 is replaced
by new access code 22351.
76
Language
1. German
5. Slovenian
2. English
6. Czech
3. French
7. Serbian
4. Dutch
8. Italian
Cancel more Enter
Selecting the panel language
Use this function to select the panel language on the
LC module. Please choose one of the numbers
offered on the LC module to select the right language.
By pressing F3 "more", other languages can be
chosen.
77
Interfaces
1. UART 1
2. UART 2
3. UART 3
4. USB
Cancel Protocol Baud rate
Configuring the interfaces
The FCP offers 3 different serial interfaces RS-232
(see wiring diagrams). UART 2 can also be used as
RS-485 interface.
For every interface a certain protocol can be
configured e.g. for printer, PC configuration etc. This
means the FCP is easily to adapt to the required
application and very flexible.
Please select UART 1, 2 or 3 by the cursor keys
↑
,
↓
and then press F2 ("Protocol")
Jump to Menu
113
After that you can configure the "baud rate” by
pressing F3
Jump to Menu
114
The USB interface will be used exclusively for
programming, reading of the event memory and
transmission of diagnosis data. The USB interface
can be disabled/enabled through the control panel to
initialise the interface or to prevent unwanted access
to the system.
78
Convent. Detect.
Loop card : 3
from ML : 1
to ML : 8
Cancel
Alarm and fault thresholds for conventional -
detectors
This function enables the user to adjust every
conventional zone individual relating alarm and fault
thresholds. So nearly every detector on the fire
market can be connected to the "Solution F1".
The conventional detector PCBs inside the "Solution
F1" are preset for Hochiki CDX detectors and Apollo
S65/Orbis.
For other detectors please have a look into their data
sheet to adjust the right values.