Chapter 4 HMI Operation Introduction
NR ELECTRIC CO., LTD.
34
counterpart operating information indirectly. Four menu items are under
STATE SHOW
and they
are detailed described in the following sections.
1) LOC.STATE
The
STATE SHOW
menu is shown in the following figure.
TYPE
LOC.
STATE DISPLAY
NORMAL RUN
Title
Operating
Status
Label
STATE
Item
STATE
Figure 4.5-2 LOC. Display
Items Signification:
Title: it is the menu items name
State Display
.
Item: Item shows the content currently displayed. It might be: LOC.,
COM
, NET and DEV.
Item can be interchanged by pressing
keys.
Operating Status: it shows the native equipment’
s current operating information. It might be:
INACTIVE RUN:
It indicates that the native equipment is working as
HOT STANDBY
MACHINE
without any internal fault been detected. It also indirectly points out that its
counterpart is working as
HOST MACHINE
.
Simultaneously, the
LED
labeled STANDBY is lit
on and a normal open contact of terminal 14-15 on
PWR
Board is being closed to indicate that
the native equipment is been in
HOT STANDBY MACHINE
mode.
NORMAL RUN:
It indicates that the native equipment is working as
HOST MACHINE
without
any internal fault been detected. It also indirectly points out that its counterpart is working as
HOT STANDBY MACHINE
or the counterpart has been in the
CLOSE DOWN
mode or
actually there isn’
t any counterpart for the native equipment at all.
FAULT RUN:
It shows although that at least one hardware or software exception has bee
detected by the device self-diagnostic facilities, the device still works as a
HOST MACHINE
.
The device needs to be handled to clear the exception.
2) NET STATE
Communication status of each Ethernet port on every
CPU
board is displayed in this menu item as
presented in the following figure. By pressing any of
keys, it is very easy to select
CPU
Number, Ethernet Port Number
or
NET
.
Summary of Contents for RCS-9698G
Page 1: ...RCS 9698G H Remote Terminal Unit Instruction Manual NR Electric Co Ltd...
Page 2: ......
Page 6: ...RCS 9698G H Remote Terminal Unit NR ELECTRIC CO LTD iv...
Page 10: ...RCS 9698G H Remote Terminal Unit NR ELECTRIC CO LTD viii...
Page 72: ...Chapter 5 Installation NR ELECTRIC CO LTD 62 ground terminal of this device...
Page 76: ...Chapter 6 Commissioning NR ELECTRIC CO LTD 66...
Page 80: ...Chapter 8 Decommissioning and Disposal NR ELECTRIC CO LTD 70...