Chapter 3 Hardware Structure and Operation Theory
NR ELECTRIC CO., LTD.
9
Chapter 3 Hardware Structure and Operation Theory
3.1 Overview
As the
RTU
of a substation or a power plant,
RCS-9698G/H
is used for the communication
between the BCUs/relay protections/
IED
s and the dispatching center/centralized control station.
RCS-9698G/H
adopt multi-
CPU
structure, each
CPU
operate independently.
RCS-9698G/H
has mass solid-state storage up to 4G/8G, up to 16/32 (single machine/dual
machine) 100M ethernet ports and supports
IRIG-B
clock synchronization.
RCS-9698G/H
supports 5 dual-machine switchover schemes, please refer to Section 4.5.3.2.
RCS-9698G/H
is based on a modular and scalable architecture to support configurable hardware
modules adapted to the plant data interfaces. The equipment allows flexibility and scalability for
the configuration of concrete applications and provides customized communication solutions.
Rear panel of
RCS-9698G
is shown in the following figure.
Figure 3.1-1 Rear panel of
RCS-9698G
Rear panel of
RCS-9698H
is shown in the following figure.
Figure 3.1-2 Rear panel of
RCS-9698H
Summary of Contents for RCS-9698G
Page 1: ...RCS 9698G H Remote Terminal Unit Instruction Manual NR Electric Co Ltd...
Page 2: ......
Page 6: ...RCS 9698G H Remote Terminal Unit NR ELECTRIC CO LTD iv...
Page 10: ...RCS 9698G H Remote Terminal Unit NR ELECTRIC CO LTD viii...
Page 72: ...Chapter 5 Installation NR ELECTRIC CO LTD 62 ground terminal of this device...
Page 76: ...Chapter 6 Commissioning NR ELECTRIC CO LTD 66...
Page 80: ...Chapter 8 Decommissioning and Disposal NR ELECTRIC CO LTD 70...