Chapter 2 Technical Data
NR ELECTRIC CO., LTD.
5
Chapter 2 Technical Data
2.1 General Specification
2.1.1 Electrical Specifications
Rated Voltage (Un)
3 options to be selected:
110V/125V DC;
220V/250V DC;
48V DC
Variation
(80% ~ 120%)Un
Ripple in the DC
auxiliary voltage
Max 15% of the DC value. Per IEC 60255-11:1979
Voltage dips and voltage
short interruptions
Per IEC 60255-11:1979
20ms for interruption without de-energizing, dips 60% of Un without
reset up to 100ms
Burden
<45W for single machine,
<90W for dual machine configuration
Backup battery type
ML2032, 3V, 65mAh
2.1.2 Mechanical Specifications
Enclosure dimensions
(W×H×D)
482.6×177.0×291.0 (unit: mm)
(IEC 4U high)
Trepanning dimensions
(W×H)
450.0×179.0(unit: mm), M6 screw
Mounting Way
Flush mounted
Weight per device
Approx. 5kg
Local control panel
37
LED
indicators, a 9-key keypad and a 80×60-dot
LCD
for single
machine,
74
LED
indicators, two independent 9-key keypads and two
independent 80×60-dot
LCD
for dual machine configuration
Housing material
Aluminum
Housing color
Silver grey
Location of terminals
Rear panel of the device
Protection class
(per IEC60529:1989)
Front side: IP40, up to 51
Rear side, connection terminals: IP20
Other Sides: IP30
Summary of Contents for RCS-9698G
Page 1: ...RCS 9698G H Remote Terminal Unit Instruction Manual NR Electric Co Ltd...
Page 2: ......
Page 6: ...RCS 9698G H Remote Terminal Unit NR ELECTRIC CO LTD iv...
Page 10: ...RCS 9698G H Remote Terminal Unit NR ELECTRIC CO LTD viii...
Page 72: ...Chapter 5 Installation NR ELECTRIC CO LTD 62 ground terminal of this device...
Page 76: ...Chapter 6 Commissioning NR ELECTRIC CO LTD 66...
Page 80: ...Chapter 8 Decommissioning and Disposal NR ELECTRIC CO LTD 70...