Chapter 2 Technical Data
NR ELECTRIC CO., LTD.
7
DNP 3.0 (serial and TCP/IP)
MODBUS
RP570
CDT
SC1801
Further protocols on request
Downward Communication
(To
SAS
)
IEC 60870-5-103 or IEC61850
2.1.6 Type Test
2.1.6.1 Environmental Tests
Dry cold test
IEC60068-2-1:1990, 16 h at -25°C
Dry heat test
IEC60068-2-2:1974, 16 h at +55°C
Damp heat test, cyclic
IEC60068-2-30:1980, two (12+12 hours) cycles, 95%RH,
low tempe25°C, high tempe55°C
2.1.6.2 Mechanical Tests
Vibration
IEC60255-21-1:1988, Class I
Shock and bump
IEC60255-21-2:1988, Class I
2.1.6.3 Electrical Tests
Dielectric tests
IEC60255-5:2000, test voltage: 2kV, 50Hz, 1min
Impulse voltage tests
IEC60255-5:2000, test voltage: 5kV, unipolar
impulses, waveform 1.2/50
μ
s, source energy 0.5J
Insulation
measurement
IEC60255-5:2000, insulation resistance >100M
Ω
, 500Vdc
2.1.6.4 Electromagnetic Compatibility
(
EMC
)
Per IEC 60255-22-1:1988
Common mode: class III 2.5kV
1MHz burst disturbance
test
Differential mode: class III 1.0kV
Per IEC60255-22-2:1996 class IV
For contact discharge: 8kV
Electrostatic discharge
test
For air discharge: 15kV
Per IEC 60255-22-3:2000 class III
Frequency sweep
Radiated amplitude-modulated
10V/m (rms), f=80… 1000MHz
Radio
frequency
interference tests
Spot frequency
Radiated amplitude-modulated
10V/m (rms), f=80MHz/160MHz/450MHz/900MHz
Radiated pulse-modulated
10V/m (rms), f=900MHz
Summary of Contents for RCS-9698G
Page 1: ...RCS 9698G H Remote Terminal Unit Instruction Manual NR Electric Co Ltd...
Page 2: ......
Page 6: ...RCS 9698G H Remote Terminal Unit NR ELECTRIC CO LTD iv...
Page 10: ...RCS 9698G H Remote Terminal Unit NR ELECTRIC CO LTD viii...
Page 72: ...Chapter 5 Installation NR ELECTRIC CO LTD 62 ground terminal of this device...
Page 76: ...Chapter 6 Commissioning NR ELECTRIC CO LTD 66...
Page 80: ...Chapter 8 Decommissioning and Disposal NR ELECTRIC CO LTD 70...