Chapter 4 HMI Operation Introduction
NR ELECTRIC CO., LTD.
55
4.5.7.1 INPUT STATE
Figure 4.5-38
INPUT STATE
This menu item is used to test binary inputs circuits on
PWR
Board by adding certain positive
voltage to relevant binary input terminal.
OPEN
means that there is certain negative voltage
(equals to negative pole of optical coupler on terminal 20
PWR
Board) on relevant binary input
terminal and switching apparatus signaled by this binary input is being in open state or inactivated.
In contrast,
CLOSE
denotes that there is certain positive voltage on relevant binary input terminal
and switching apparatus signaled by this binary input is being in closing state or activated.
NOTE
:
If the status of ”
IN1
”is “
CC_Ctrl
”
, it indicates that the control commands from
control centers are enabled, .but the control commands from local HMI system(i.e.:
SCADA) are disabled.
If the status of ”
IN1
”is “
ST_Ctrl
”
, it indicates that the control commands from control
centers are disabled, .but the control commands from local HMI system(i.e.: SCADA) are
enabled.
4.5.7.2 OUTPUT TEST
Figure 4.5-39
OUTPUT TEST
This menu item is used to check the binary output relays, testing whether binary output functions
are operational. Press
keys to select expected output relay and push
key to
Summary of Contents for RCS-9698G
Page 1: ...RCS 9698G H Remote Terminal Unit Instruction Manual NR Electric Co Ltd...
Page 2: ......
Page 6: ...RCS 9698G H Remote Terminal Unit NR ELECTRIC CO LTD iv...
Page 10: ...RCS 9698G H Remote Terminal Unit NR ELECTRIC CO LTD viii...
Page 72: ...Chapter 5 Installation NR ELECTRIC CO LTD 62 ground terminal of this device...
Page 76: ...Chapter 6 Commissioning NR ELECTRIC CO LTD 66...
Page 80: ...Chapter 8 Decommissioning and Disposal NR ELECTRIC CO LTD 70...