background image

User Manual

ADAM-3600-C2G

iRTU User’s Manual

Summary of Contents for ADAM-3600-A1FN0AE

Page 1: ...User Manual ADAM 3600 C2G iRTU User s Manual ...

Page 2: ...Advantech assumes no liability under the terms of this warranty as a consequence of such events Because of Advantech s high quality control standards and rigorous testing most of our customers never need to use our repair service If an Advantech product is defec tive it will be repaired or replaced at no charge during the warranty period For out of warranty repairs you will be billed according to ...

Page 3: ...hen using any ADAM module Technical Support and Assistance 1 Visit the Advantech web site at www advantech com support where you can find the latest information about the product 2 Contact your distributor sales representative or Advantech s customer service center for technical support if you need additional assistance Please have the following information ready before you call Product name and s...

Page 4: ...ADAM 3600 Series User Manual iv ...

Page 5: ...12 Figure 3 2 Analog Input Wiring 12 Figure 3 3 Digital Input Wiring 13 Figure 3 4 Digital Output Wiring 13 3 1 3 Serial Port Wiring 13 Figure 3 5 Serial Port Wiring 13 3 2 Installation 14 3 2 1 Wall mounted and DIN Rail Installation 14 Figure 3 6 Wall mounted Installation 14 Figure 3 7 DIN Rail Installation 14 3 2 2 Wireless Module Installation 15 Figure 3 8 Wireless Module Installation 15 3 2 3 ...

Page 6: ... Figure 4 19User Tag Configuration 33 4 2 3 Data Logger Configuration 34 Figure 4 20Historical recording data configuration 34 4 2 4 Protocol Service Configuration 34 Figure 4 21Adding I O Tags to the Modbus Address List 35 Figure 4 22Adding I O Tag Information 35 Figure 4 23WebAccess whereIAM 36 4 2 5 Connectivity Configuration 36 Figure 4 24Relationship among connection period connection du rati...

Page 7: ...vii ADAM 3600 Series User Manual Appendix B Interface Definition 47 B 1 Interface Definitions 48 B 1 1 Communication Ports 48 B 1 2 I O Interface Definition 50 ...

Page 8: ...ADAM 3600 Series User Manual viii ...

Page 9: ...Chapter 1 1 Introduction ...

Page 10: ...s extremely costly Intelligent RTU can perform remote monitor ing operation maintenance and updates via the Internet iRTU can perform up date complete delivery tasks at the site and update data to the cloud iRTU can also com municate with each other quickly handle I O correlation on emergencies to reduce the loss The ADAM 3600 has a high performance and low power processor adopts 20 local I O poin...

Page 11: ...Chapter 2 2 Specifications ...

Page 12: ...oC 70oC The selected components are industrial grade and have been tested with the strictest environmental control to ensure that the products have a long life and stable working in harsh environments Convenient remote project configuration software iRTU Studio Provides project configuration software with remote operation Users can configure all the devices in an offline and group mode and can aut...

Page 13: ... to identify the health status of communications lines remotely monitor the com munication quality through the network in group mode conduct the maintenance in advance so as to avoid emergency repair caused by temporary failure 2 2 ADAM 3600 C2G Specification 2 2 1 ADAM 3600 C2G Specification of Main Unit 2 2 1 1 System Specifications CPU A8 AM3352BZCZD60 RAM DDR3 256MB Battery Backup RAM 32KB Pow...

Page 14: ... Hz 120 dB NMR 50 60 Hz 100 dB Span Drift 25 ppm O C Zero Drift 3 μV O C 3 μA O C Isolation Voltage 2 000VDC Burn out detection Yes Current only Digital Input Pulse Input Channel 8 Input Type Sink Wet Contact Counter Wet Contact Input Logic0 0 5 VDC Logic 1 11 30VDC Rated Voltage 12 24VDC Rated Input Current 5mA 12VDC 10mA 24VDC Input Filter Programmable Default 3ms Pulse Input Frequency 150HZ Ove...

Page 15: ...dB NMR 50 60 Hz 100 dB Span Drift 25 ppm O C Zero Drift 3 μV O C 3 μA O C Isolation Voltage 2000VDC Burn out detection Yes Current only Channel 3 differential Input Type J K T E R S B Type Thermocouple Resolution 16 bit Sampling rate 10 samples second total Input Impedance 2M Accuracy 0 1 or better Full Scale CMR 50 60 Hz 90dBs NMR 50 60 Hz 60dBs Span Drift 25 ppm O C Zero Drift 3 μV OC Isolation ...

Page 16: ... 5mA 12VDC 10mA 24VDC Input Filter Programmable Default 3ms Pulse Input Frequency 150HZ Over Voltage Protection 40 VDC Channel 8 Output Type Open Collector Sink OC Output Rated Voltage 8 30 VDC Rated Current 200 mA max load Over Voltage Protection 40 VDC Pulse Output Frequency 1KHz Isolation Voltage 2000 VDC Channel 4 Output Type Open Collector Sink OC Output Rated Voltage 8 30 VDC Rated Current 2...

Page 17: ...tion DI0 Green Light on the channel is activated by input signal DI1 Green DI2 Green DI3 Green DI4 Green DI5 Green DI6 Green DI7 Green DO0 Green Light on the channel output is activated DO1 Green DO2 Green DO3 Green LED Color Function Description TX1 Orange Blinking COM1 is sending data RX1 Green Blinking COM1 is receiving data TX2 Orange Blinking COM2 is sending data RX2 Green Blinking COM2 is re...

Page 18: ...ADAM 3600 Series User Manual 10 2 4 iRTU Dimensions Figure 2 2 ADAM 3600 Dimensions ...

Page 19: ...Chapter 3 3 Wiring and Installation ...

Page 20: ...put ranging from 10 VDC to 30 VDC Users can choose standard 12 VDC or 24 VDCC power supply Figure 3 1 Power Supply Wiring 3 1 2 3 1 2Input Output Wiring 3 1 2 1 Analog Input Wiring ADAM 3600 C2G equips with 8 channels AI with differential wiring type wire as shown below Figure 3 2 Analog Input Wiring ...

Page 21: ...Normally user can leave it empty and consider wiring while the field interference is significant Figure 3 3 Digital Input Wiring 3 1 2 3 Digital Output Wiring ADAM 3600 C2G is equipped with 4 channels DO follow the below diagram for wir ing Figure 3 4 Digital Output Wiring 3 1 3 Serial Port Wiring ADAM 3600 C2G is equipped with 3 serial ports the COM2 3 are for RS 485 and locate on the orange term...

Page 22: ...on Wall mounted and DIN Rail Installation For wall mounted installation users can fix the device on the wall with 4 screws as shown below Figure 3 6 Wall mounted Installation For DIN Rail installation follow the below diagram to put the device on the DIN Rail and lock the 3 lock to fix the device on the DIN Rail Figure 3 7 DIN Rail Installation ...

Page 23: ...d while the upper supports full size card Two screws are needed to install each card and then the antenna could be installed More details as follows Figure 3 8 Wireless Module Installation 3 2 3 Expansion Input Output Module Installation The ADAM 3600 C2G has four expansion slots named A B C and D with a black cover The following is the installation methods when customers need to plug expan sion m...

Page 24: ...re 3 11 Writeable Label 3 2 5 SD Card Installation The ADAM 3600 C2G supports two types of SD cards used as storage One is Micro SD which carries the OS The other is a Standard SD for storing data It is available for users to choose and configure The installation location of Standard SD is at the bottom of the antenna poke the black blade upward and you will find the slot insert the SD card push t...

Page 25: ...r 3 Wiring and Installation 3 2 6 SIM Card Installation When customers install a 3G GPRS module they need to insert a SIM card follow below diagram to install the SIM card The SIM card is micro SIM 3FF type Figure 3 13 SIM Card Installation ...

Page 26: ...3600 C2G IO has two DIP switches as follows Figure 3 14 DIP Switch Setting No Name Meaning Description 1 SW6 Node ID 6 bit supports 0 63 devices ON 1 OFF 0 1 is for high bit 6 is for last bit ex 0 0 0 0 0 1 1 1 0 0 0 0 0 32 2 SW5 8 ch AI Current or voltage range select ON Current OFF Voltage ...

Page 27: ...and Installation 3 3 2 Jumper Settings The ADAM 3600 CPU has two Jumpers as follows Figure 3 15 Jumper Settings No Name Meaning Descriptions 1 CN14 COM1 DB9 Port select RS 232 or RS 485 RS 485 RS 232 2 CN15 Watchdog Enable Jumper ON Enable OFF Disable ...

Page 28: ...ADAM 3600 Series User Manual 20 ...

Page 29: ...Chapter 4 4 Advantech iRTU Studio ...

Page 30: ...omplete the settings for Ethernet Wi Fi 3G and GPRS via iRTU Studio ADAM 3600 provides Modbus RTU Modbus TCP and DNP3 0 servers and customers can flexibly choose protocol services according to their own needs Advantech iRTU Studio Support remote monitoring of communication status of serial ports and Ethernet ports Advantech iRTU Studio can be downloaded from Advantech support website http support ...

Page 31: ... 3 After finish the device adding user s can modify the device information by double click the device name on the left hand side tree view or right click on the device name and choose edit Figure 4 2 Adding Devices and Editing 4 2 1 3 Copying Devices To reduce the complexity of configure a lot of ADAM 3600 on the field iRTU Studio supports the ability to copy device information within a project Us...

Page 32: ...acquisition which is an important functionality for a RTU Through this interface user can manage all the ADAM 3600 resources which are able to fetch data from the field site The ADAM 3600 can support many interfaces for data acquisition include on board I O expansion I O serial device I O Ethernet device IO and Wireless Zigbee device I O All these above I Os can be configured as a tag by using the...

Page 33: ...nfiguration Configuration of the discrete onboard IO is identical with analog configuration except that it has no advanced configuration Moreover ADAM 3600 C2G s on board DI and DO could separately provide counter and Pulse Width Modulation PWM function Users can set these functions as described in 4 2 6 2 After selecting Counter and PWM functions users have to configure them through iRTU Studio T...

Page 34: ...he data type is discrete and the value can only be 0 or 1 Users can set the initial value and signal reverse When the signal reverse is True it means that DO interface enable the PWM function with value of 1 Otherwise when the signal reverse is False it means that DO interface enable the PWM function with the value of 0 PWM_HI the duration time of PWM high level The data type is analog of 32 bits ...

Page 35: ...n Apply the port will be created on the left hand side tree view under the Data Center item Figure 4 8 Adding COM port 4 Right click the COMx item created on the previous step and select Add Meter to add meter 5 In the New Meter page type in the name and related parameters and click Apply to add meter While the meter added there is a new item I O Tag below the meter click the in front of the COM p...

Page 36: ...s shown in the following figure to edit the port Figure 4 10 Editing TCP Information 2 Right click TCP item choose Delete the port will be deleted after your confir mation 3 Right click TCP item choose Add Meter to add a meter 4 In the New Meter page type in the name and related parameters and click Apply to add meter While the meter added there is a new item I O Tag below the meter click the in f...

Page 37: ...g a TCP Meters I O 6 iRTU Studio default provide 1 TCP port for Ethernet IO configuration if user need another TCP port please right click on the Data Center and select Add Port 7 In the Type field of New Port page select TCPIP and input the related parameters for the serial port Then click button Apply a new TCP port will be created Figure 4 13 Adding and Editing TCP Ports ...

Page 38: ...hich is the supported Zigbee driver for ADAM 3600 3 In the section of Serial Port Setting please select the port where the Zigbee communication module connects to and adjust related parameter to communi cate with the module Please note if the resource is shown on the tree view it is occupied by other meter the resource will not be shown on the drop down menu of the Port field 4 Click button Apply ...

Page 39: ... added there is a new item I O Tag below the meter click the in front of the port and meter to unfold it Figure 4 15 Adding a ZigBee Meter 7 Double click the I O Tag item to edit the tag to map with the data from Zigbee wireless meter Figure 4 16 ZigBee Meter I O Configuration 8 To delete a Zigbee port or a meter right click to the select the target item and select Delete ...

Page 40: ...er tags With computation tag configuration function users do not need to program and just configure it through iRTU Studio iRTU Studio provides many operations including basic arithmetic simple functions trigono metric functions logical judgements Boolean operations etc The specific operation flow is as follows 1 Firstly select the acquisition tag represented by A B C D respectively Figure 4 17 Ad...

Page 41: ...n which allow users to choose and configure This is called as user tag These user tags could be used for C language and KW language program ming as a control signal as well as a presentation of computation results In a word all of these user tags will fulfill user s demands for data iRTU Studio supports user tag configuration Users can configure step by step into RTU as shown in the following Figu...

Page 42: ...ch customer service We will help you to read the data Figure 4 20 Historical recording data configuration 4 2 4 Protocol Service Configuration The ADAM 3600 C2G is an open basis intelligent RTU which is able to integrate many kinds of communication protocol to communicate with the center station And it is default with two standard protocol services Modbus and DNP3 4 2 4 1 Modbus Service The ADAM 3...

Page 43: ...ags to the Modbus Address List Figure 4 22 Adding I O Tag Information To connect with WebAccess users should click WebAccess WhereIAm Make sure that the physical IP address with WebAccess is right The parameter definition as below IP Address physical IP address with WebAccess Port default TCP port for WebAccess Period s for connecting with WebAccess Center ...

Page 44: ...onnection function and users can configure the parameters in iRTU Studio The specific configured parameters include Protocol There are two optional protocols DTU Four Faith PROT and Webac cess WhereIAm in the case of the upper station is Webaccess The specific operation will be different under different protocols which will be described below Local Service Modbus RTU and Modbus TCP Binding Interfa...

Page 45: ...M Card Number Here are 11 card numbers Heart Beat Period It specifies the sending period of heartbeat char When it is set as 0 it means that heart beat char is not transmitted Moreover it has four kinds of chars escape char heart beat char escaped heart beat char and escaped escape char Escape rules The heartbeat character is only for heart beat packet The heart beat char can be escaped as escape ...

Page 46: ... two parts I O setting and network setting 4 2 6 1 I 0 Settings The ADAM 3600 C2G is equipped with 8 AI channels 8 DI channels and 4 DO channels Besides there are four I O expansion slots which can integrate various I O modules into the main unit In the Studio for both on board I O and expansion I O user can set mode I O range integration time as well as calibration Configure the I O setting as be...

Page 47: ...Expansion I O Settings Click the button Calibration to execute the calibration function for the analogue input chan nel on board User has to provide the precious source for the zero and span calibration User only need to calibrate the channel 0 the related parameter will apply to all other channels automatically Please follow the instruction to finish the calibration Note The analogue I O is defau...

Page 48: ...xed IP If users select RTU as DHCP mode RTU will provide a default IP address when not getting an IP address Figure 4 29 Wired Network Settings Wireless Network Settings In the Wi Fi setting section users have to input an SSID to join the network For the network security there are three mechanisms available Open No password needed the RTU will auto connect to the Wi Fi network WEP A kind of networ...

Page 49: ...ure the Connect has been clicked Figure 4 31 GPRS Settings If there are different communicated modes applied Users should make scripts Figure 4 32 GPRS Script Setting 4 2 6 3 LED Configuration The ADAM 3600 C2G has many system status indicators Users can configure LED indica tors through iRTU Studio to make it blink according to users definition Figure 4 33 LED configuration ...

Page 50: ...nnection PROG indicator can be applied The wireless signal includes GPRS 3G 4G signal and Wi Fi signal Users can select depends on different requirements Long light means the signal is good blinking means the signal is normal and off means the signal is bad ERROR Indicator Configuration Users can also enable ERROR indicator to ensure the correctness of data recording and communication connection f...

Page 51: ...s on line If the NodeID setting is incorrect or the device is actu ally not in the network the status will show off line Figure 4 34 Identification for Connected RTU Devices 4 3 2 Project Download While all the RTU devices are no line click Project Download to download the project into the RTU devices If users click and active the project node on the left hand side tree view and click the Project ...

Page 52: ...he password follow the steps below 1 iRTU Studio connects with the RTU device and it has been identified 2 Click password setting select the device input the old and new password respectively and then confirm the new password 3 Back to the General Information of the RTU device edit password to ensure it fit the new password Please note the Project download will not work if the password does not ma...

Page 53: ...Appendix A A ADAM 3600 Naming Rules ...

Page 54: ... 3600 A1F and ADAM 3600 C2G which shows a difference as far as their design and features In this Manual we focus on the introductions of ADAM 3600 C2G Figure A 1 ADAM 3600 Naming Rules Examples ADAM 3600 C2GL1AE Cortex A8 iRTU for Oil Gas C Series ADAM 3600 A1FN0AE Cortex M4 Remote IO for Facility Monitoring A Series ...

Page 55: ...Appendix B B Interface Definition ...

Page 56: ...S232 signals RxD TxD GND RTS CTS RS485 signals DATA DATA B 1 1 2 COM 2 COM3 RS 485 Connection Terminal Block Baud rate 1200 921 6k bps RS 485 signals DATA DATA Communication Isolation 2000VDC PIN RS 232 Signal 1 N C 2 RXD 3 TXD 4 N C 5 GND 6 N C 7 RTS 8 CTS 9 N C PIN RS 485 Signal 1 DATA 2 DATA 3 N C 4 N C PIN RS 485 Signal 1 DATA2 2 DATA2 3 DATA3 4 DATA3 ...

Page 57: ...t Connection USB 2 0 1800 connect USB signals Vcc Data Data GND B 1 1 4 LAN1 and LAN2 Ethernet Port Connection RJ 45 Base T 1800 connect Transfer rate 10 100Mbps LAN signals TD TD RD RD PIN USB Signal 1 VCC 2 Data 3 Data 4 GND PIN Signal 1 TD 2 TD 3 RD 4 N C 5 N C 6 RD 7 N C 8 N C ...

Page 58: ...ADAM 3600 Series User Manual 50 B 1 2 I O Interface Definition ...

Page 59: ...51 ADAM 3600 Series User Manual Appendix B Interface Definition ...

Page 60: ...ations are subject to change without notice No part of this publication may be reproduced in any form or by any means electronic photocopying recording or otherwise without prior written permis sion of the publisher All brand and product names are trademarks or registered trademarks of their respective companies Advantech Co Ltd 2015 ...