7 Settings
PCS-978 Transformer Relay
7-29
Date: 2013-01-16
Item
Description
SNTP(BC): Broadcast SNTP mode via Ethernet network.
Message (IEC103): Clock messages through IEC103 protocol.
Advanced
IEEE1588: Clock message via IEEE1588.
IRIG-B(Fiber): IRIG-B via optical-fibre interface.
PPS(Fiber): Pulse per second (PPS) via optical-fibre interface.
NoTimeSyn
When no time synchronization signal is connected to the equipment, please select
this option and the alarm message [Alm_TimeSync] will not be issued anymore.
“Conventional” mode and “SAS” mode are always be supported by device, but “Advanced” mode
is only supported when NET-DSP module is equipped. The alarm signal [Alm_TimeSyn] may be
issued to remind user loss of time synchronization signals.
1)
When “SAS” is selected, if there is no conventional clock synchronization signal, the device
will not send the alarm signal [Alm_TimeSyn]. When “Conventional” mode is selected, if there
is no conventional clock synchronization signal, “SAS” mode will be enabled automatically
with the alarm signal [Alm_TimeSyn] being issued simultaneously.
2)
When “Advanced” mode is selected, if there is no conventional clock synchronization signal
connected to NET-DSP module
,
“SAS” mode is enabled automatically with the alarm signal
[Alm_TimeSyn] being issued simultaneously.
3)
When “NoTimeSyn” mode is selected, the device will not send alarm signals without
NOTE!
The clock message via IEC103 protocol is invalid when the device receives the
IRIG-B signal through RC-485 port.
7.
[IP_Server_SNTP]
It is the address of the SNTP time synchronization server which sends SNTP timing messages to
the relay or BCU.
8.
[OffsetHour_UTC], [OffsetMinute_UTC]
When the IEC61850 protocol is adopted in substations, if the time tags of communication
messages are required according to Universal Time Coordinated (UTC), the two settings are
used to set the local time of a country or area where the relay is installed. If there is no such a
requirement, the two settings must be set as “0”.
Example 1: In China where UTC offset is UTC +8:00, [OffsetHour_UTC] and [OffsetMinute_UTC]
should be set as “8hrs” and “0min” respectively.
Example 2: In Argentina where UTC offset is UTC-3:00, [OffsetHour_UTC] and
[OffsetMinute_UTC] should be set as “-3hrs” and “0min” respectively.
Example 3: In Nepal where UTC offset is UTC +5:45, [OffsetHour_UTC] and [OffsetMinute_UTC]
should be set as “+5hrs” and “45min” respectively.
Summary of Contents for PCS-978
Page 1: ...PCS 978 Transformer Relay Instruction Manual NR Electric Co Ltd ...
Page 2: ......
Page 6: ...Preface PCS 978 Transformer Relay IV Date 2013 01 16 ...
Page 10: ...Preface PCS 978 Transformer Relay VIII Date 2013 01 16 ...
Page 62: ...3 Operation Theory PCS 978 Transformer Relay 3 p Date 2013 01 16 ...
Page 250: ...4 Supervision PCS 978 Transformer Relay 4 b Date 2013 01 16 ...
Page 264: ...4 Supervision PCS 978 Transformer Relay 4 14 Date 2013 01 16 ...
Page 266: ...5 Management PCS 978 Transformer Relay 5 b Date 2013 01 16 ...
Page 272: ...5 Management PCS 978 Transformer Relay 5 6 Date 2013 01 16 ...
Page 334: ...6 Hardware Description PCS 978 Transformer Relay 6 60 Date 2013 01 16 ...
Page 370: ...8 Human Machine Interface PCS 978 Transformer Relay 8 d Date 2013 01 16 ...
Page 404: ...8 Human Machine Interface PCS 978 Transformer Relay 8 34 Date 2013 01 16 ...
Page 406: ...9 Configurable Function PCS 978 Transformer Relay 9 b Date 2013 01 16 ...
Page 446: ...10 Communication PCS 978 Transformer Relay 10 26 Date 2013 01 16 ...
Page 448: ...11 Installation PCS 978 Transformer Relay 11 b Date 2012 10 09 ...
Page 456: ...11 Installation PCS 978 Transformer Relay 11 8 Date 2012 10 09 ...
Page 458: ...12 Commissioning PCS 978 Transformer Relay 12 b Date 2012 12 07 ...
Page 468: ...12 Commissioning PCS 978 Transformer Relay 12 10 Date 2012 12 07 ...
Page 470: ...13 Maintenance PCS 978 Transformer Relay 13 b Date 2012 10 09 ...
Page 474: ...13 Maintenance PCS 978 Transformer Relay 13 4 Date 2012 10 09 ...
Page 476: ...14 Decommissioning and Disposal PCS 978 Transformer Relay 14 b Date 2012 10 09 ...
Page 478: ...14 Decommissioning and Disposal PCS 978 Transformer Relay 14 2 Date 2012 10 09 ...
Page 480: ...15 Manual Version History PCS 978 Transformer Relay 15 2 Date 2013 01 16 ...