3 Operation Theory
PCS-978 Transformer Relay
3-125
Date: 2013-01-16
No.
Setting Item
Range
Step
Unit
Description
protection.
2
x.50/51P4.K_Iset
10~40
0.001
Multiple of the maximum operating current to the
pickup setting of stage 4 of phase overcurrent
protection.
3
x.50/51P4.t_Op
0~3600
0.001
s
Time delay of stage 4 of phase overcurrent
protection.
4
x.50/51P4.TMS
0.05~3.2
0.001
Time multiplier setting of stage 4 of phase
overcurrent protection.
5
x.50/51P4.tmin
0~20
0.001
s
Minimum delay of stage 4 of phase overcurrent
protection.
6
x.50/51P4.K
0~120
0.001
The constant K of stage 4 of phase overcurrent
protection.
7
x.50/51P4.C
0~20
0.001
s
The constant C of stage 4 of phase overcurrent
protection.
8
x.50/51P4.Alpha
0.02~5
0.001
The exponent alpha of stage 4 of phase
overcurrent protection.
9
x.50/51P4.Opt_Curve
0~13
1
Logic setting for selecting operating characteristic
curve of stage 4 of phase overcurrent protection.
Please refer to
Section 3.12.3.3
10
x.50/51P4.En_VCE
0: disable
1: enable
1
Logic setting of enabling voltage control element
for phase overcurrent protection.
11
x.50/51P4.Opt_Dir
0~2
1
Logic setting of selecting control mode of
directional element to stage 4 of phase overcurrent
protection.
0: no direction;
1: forward direction;
2: reverse direction
12
x.50/51P4.En_Hm2_Blk
0: disable
1: enable
1
Logic setting of enabling harmonic blocking stage
4 of phase overcurrent protection.
0: disable; 1: enable
13
x.50/51P4.En
0: disable
1: enable
1
Logic setting of enabling stage 4 of phase
overcurrent protection.
0: disable; 1: enable
14
x.51P4.OutMap
0000~FFFF
Tripping logic setting of stage 4 of phase
overcurrent protection.
NOTE!
If the minimum operating time [
x.
50/51P4
.tmin] is set to “0”, the maximum
operating current is valid, and the setting
[x.
50/51P4.K_Iset] can be set according to
requirements. If the current is greater than [
x.
50/51P4.K_Iset]x[
x.
50/51P4.I_Set], the
operating time of IDMT becomes flat, i.e. the operating time is equal to the operating
time of IDMT at the point current equal to [
x.
50/51P4.K_Iset]x[
x.
50/51P4.I_Set]. If
Summary of Contents for PCS-978
Page 1: ...PCS 978 Transformer Relay Instruction Manual NR Electric Co Ltd ...
Page 2: ......
Page 6: ...Preface PCS 978 Transformer Relay IV Date 2013 01 16 ...
Page 10: ...Preface PCS 978 Transformer Relay VIII Date 2013 01 16 ...
Page 62: ...3 Operation Theory PCS 978 Transformer Relay 3 p Date 2013 01 16 ...
Page 250: ...4 Supervision PCS 978 Transformer Relay 4 b Date 2013 01 16 ...
Page 264: ...4 Supervision PCS 978 Transformer Relay 4 14 Date 2013 01 16 ...
Page 266: ...5 Management PCS 978 Transformer Relay 5 b Date 2013 01 16 ...
Page 272: ...5 Management PCS 978 Transformer Relay 5 6 Date 2013 01 16 ...
Page 334: ...6 Hardware Description PCS 978 Transformer Relay 6 60 Date 2013 01 16 ...
Page 370: ...8 Human Machine Interface PCS 978 Transformer Relay 8 d Date 2013 01 16 ...
Page 404: ...8 Human Machine Interface PCS 978 Transformer Relay 8 34 Date 2013 01 16 ...
Page 406: ...9 Configurable Function PCS 978 Transformer Relay 9 b Date 2013 01 16 ...
Page 446: ...10 Communication PCS 978 Transformer Relay 10 26 Date 2013 01 16 ...
Page 448: ...11 Installation PCS 978 Transformer Relay 11 b Date 2012 10 09 ...
Page 456: ...11 Installation PCS 978 Transformer Relay 11 8 Date 2012 10 09 ...
Page 458: ...12 Commissioning PCS 978 Transformer Relay 12 b Date 2012 12 07 ...
Page 468: ...12 Commissioning PCS 978 Transformer Relay 12 10 Date 2012 12 07 ...
Page 470: ...13 Maintenance PCS 978 Transformer Relay 13 b Date 2012 10 09 ...
Page 474: ...13 Maintenance PCS 978 Transformer Relay 13 4 Date 2012 10 09 ...
Page 476: ...14 Decommissioning and Disposal PCS 978 Transformer Relay 14 b Date 2012 10 09 ...
Page 478: ...14 Decommissioning and Disposal PCS 978 Transformer Relay 14 2 Date 2012 10 09 ...
Page 480: ...15 Manual Version History PCS 978 Transformer Relay 15 2 Date 2013 01 16 ...