![NR Electric PCS-978 Instruction Manual Download Page 269](http://html1.mh-extra.com/html/nr-electric/pcs-978/pcs-978_instruction-manual_1713963269.webp)
5 Management
PCS-978 Transformer Relay
5-3
Date: 2013-01-16
Access path:
Main Menu
->
Measurements
->
Measurement3
->
Temp
Measurement3
No.
Symbol
Definition
Unit
1
26.Temp_PhA
Calculated temperature of phase A signal from transducer input.
°C
2
26.Temp_PhB
Calculated temperature of phase B signal from transducer input.
°C
3
26.Temp_PhC Calculated temperature of phase C signal from transducer input.
°C
5.3 Event & fault Records
5.3.1 Introduction
The protection equipment provides the following recording functions:
Event recording
Disturbance and fault recording
Present recording
All the recording information except waveform can be viewed on local LCD or by printing.
Waveform must be printed or be extracted using PCS-Explorer software and a waveform software.
5.3.2 Event Recording
The equipment can store 1024 abnormality alarm reports, 1024 binary input stage changing
reports respectively. All the records are stored in non-volatile memory, and when the available
space is exhausted, the oldest report will be automatically overwritten by the latest one
Abnormality alarm reports
An abnormality alarm being detected during relay self-check supervision or an alarm of secondary
circuit abnormality or protection alarm element will also be logged as individual events.
Binary input status changing reports
When binary input status changes, the change information will be displayed on LCD and logged as
binary input change report at the same time.
5.3.3 Disturbance and Fault Recording
5.3.3.1 Application
Use the disturbance recorder to achieve a better understanding of the behavior of the power
network and related primary and secondary equipment during and after a disturbance. An analysis
of the recorded data provides valuable information that can be used to improve existing equipment.
This information can also be used when planning for new installations.
5.3.3.2 Design
Disturbance recorder is consisted of tripping report and fault waveform. Disturbance recorder is
Summary of Contents for PCS-978
Page 1: ...PCS 978 Transformer Relay Instruction Manual NR Electric Co Ltd ...
Page 2: ......
Page 6: ...Preface PCS 978 Transformer Relay IV Date 2013 01 16 ...
Page 10: ...Preface PCS 978 Transformer Relay VIII Date 2013 01 16 ...
Page 62: ...3 Operation Theory PCS 978 Transformer Relay 3 p Date 2013 01 16 ...
Page 250: ...4 Supervision PCS 978 Transformer Relay 4 b Date 2013 01 16 ...
Page 264: ...4 Supervision PCS 978 Transformer Relay 4 14 Date 2013 01 16 ...
Page 266: ...5 Management PCS 978 Transformer Relay 5 b Date 2013 01 16 ...
Page 272: ...5 Management PCS 978 Transformer Relay 5 6 Date 2013 01 16 ...
Page 334: ...6 Hardware Description PCS 978 Transformer Relay 6 60 Date 2013 01 16 ...
Page 370: ...8 Human Machine Interface PCS 978 Transformer Relay 8 d Date 2013 01 16 ...
Page 404: ...8 Human Machine Interface PCS 978 Transformer Relay 8 34 Date 2013 01 16 ...
Page 406: ...9 Configurable Function PCS 978 Transformer Relay 9 b Date 2013 01 16 ...
Page 446: ...10 Communication PCS 978 Transformer Relay 10 26 Date 2013 01 16 ...
Page 448: ...11 Installation PCS 978 Transformer Relay 11 b Date 2012 10 09 ...
Page 456: ...11 Installation PCS 978 Transformer Relay 11 8 Date 2012 10 09 ...
Page 458: ...12 Commissioning PCS 978 Transformer Relay 12 b Date 2012 12 07 ...
Page 468: ...12 Commissioning PCS 978 Transformer Relay 12 10 Date 2012 12 07 ...
Page 470: ...13 Maintenance PCS 978 Transformer Relay 13 b Date 2012 10 09 ...
Page 474: ...13 Maintenance PCS 978 Transformer Relay 13 4 Date 2012 10 09 ...
Page 476: ...14 Decommissioning and Disposal PCS 978 Transformer Relay 14 b Date 2012 10 09 ...
Page 478: ...14 Decommissioning and Disposal PCS 978 Transformer Relay 14 2 Date 2012 10 09 ...
Page 480: ...15 Manual Version History PCS 978 Transformer Relay 15 2 Date 2013 01 16 ...