Type Codes
Type Codes for Output Devices
126
NFS-3030 Programming Manual P/N 51345:C 11/4/03
G.4 Type Codes for Output Devices
This section provides a list of Type Codes for SLC control module points and panel circuit output
module points. Select from these codes to define the type of point
Note: Do not assign Releasing Type Codes to panel circuit module points.
Appendix Table G-3 SLC Control Module and Panel Circuit Output Module Type Codes
Type Code
Silenceable
(Y=yes
N=no)*
Switch
Inhibit
(Y=yes,
N=No)*
Walk
Test
(Y=yes,
N=No)*
SLC or Panel Circuit
Output Point
Device Function
CONTROL
Y
N
Y
NAC
Supervised NAC
RELAY
Y
N
Y
Relay
Relay output
BELL CIRCUIT
Y
N
Y
NAC
Supervised NAC
STROBE CKT
Y
N
Y
NAC
Supervised NAC
HORN CIRCUIT
Y
N
Y
NAC
Supervised NAC
AUDIBLE CKT
Y
N
Y
NAC
Supervised NAC
SPEAKER
Y
N
Y
NAC
Supervised NAC for speaker circuits
blank
Y
N
Y
NAC
Supervised NAC for undefined device
NONRESET CTL
N
N
N
Relay or NAC
Supervised output, unaffected by “System Reset” command
TELEPHONE
N
N
N
Relay
Supervised Telephone circuit
CONTROL NAC
Y
N
Y
NAC
Supervised NAC
ISOLATED NAC
Y
N
Y
NAC
Supervised NAC for notification appliance, used with audio
isolators. Activates even if there is a short on its NAC circuit.
For ULC installations only.
ISOLATED SPK
Y
N
Y
NAC
Supervised NAC for speaker circuits, used with audio isolators.
Activates even if there is a short on its audio circuit. For ULC
installations only.
GEN ALARM
N
Y
Y
NAC
Control Module, XPC-8, or an XP5-C (in NAC mode) configured as
a Municpal Box Transmitter for NFPA 72 Auxiliary Fire Alarm
Systems applications (MBT-1 required). This Type ID can also be
used for general alarm activation.
GEN SUPERVIS
N
Y
Y
NAC
Control Module, XPC-8, or an XP5-C (in NAC mode) activated
under any Supervisory condition (includes sprinkler type).
GEN TROUBLE
N
Y
Y
NAC
Control Module, XPC-8, or an XP5-C (in NAC mode) activated
under any System Trouble condition.This device will not turn ON
when it is in trouble (short or open).
GENERAL PEND
N
Y
Y
NAC
Control Module XPC-8 circuit, or an XP5-C (in NAC mode) that
will activate upon receipt of an alarm and/or trouble condition,
and remain in the ON state until all events have been
ACKNOWLEDGED. This device will not turn ON when it is in
trouble (short or open)
TROUBLE PEND
N
Y
Y
NAC
Control Module or an XP5-C (in NAC mode) that will activate upon
receipt of a trouble condition, and remain in the ON state until all
troubles have been ACKNOWLEDGED. This device will not turn
ON when it is in trouble (short or open).
ALARMS PEND
N
Y
Y
NAC
Control module/panel circuit or NAC for output that will
activate upon receipt of an alarm condition, and remain in the
alarm state until all alarms have been acknowledged.
INST RELEASE
N
Y
N
NAC (SLC only)
Supervised for open circuits and ground faults. Short = normal
REL. FORM C
N
Y
N
Form-C relay (SLC only) Directs relay outputs to perform a releasing function.
RELEASE CKT
N
Y
N
NAC (SLC only)
Directs outputs to perform a releasing function.
REL CKT ULC
N
Y
N
NAC (SLC only)
Directs outputs to perform a release function as required by
ULC.
REL END BELL
N
Y
N
NAC
Activates NAC audio or visual device when releasing circuits
shut off.
REL AUDIBLE
Y
Y
N
NAC
Activates audio or visual devices steady when releasing starts.
FORM C RESET
N
Y
N
Form-C Relay (SLC only)
Control module used to interrupt 24V power to four-wire
conventional detectors for 30 seconds upon reset. Used in
conjunction with a monitor module with a conventional detector
Type ID
* Values represent program defaults.
www.PDF-Zoo.com
Summary of Contents for NFS-3030/E
Page 60: ...Program Autoprogram Menu 60 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Page 128: ...Type Codes FlashScan Codes 128 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Page 134: ...Glossary Glossary 134 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Page 142: ...NFS 3030 Programming Manual P N 51345 C 11 4 03 142 INDEX www PDF Zoo com...