Detector Status Display
AWACS™ Applications
NFS-3030 Programming Manual P/N 51345:C 11/4/03
113
The first field displays the point control. There are three designations that could appear in this field
The second field displays the point status. There are two designations that could appear in this field.
The device is a detector (an input device) so by referring to the descriptions below, it can be
determined that the point is in a normal state.
Inputs: (detectors, monitor modules, zones)
If the point is not in trouble or disabled, and the point is automatically controlled by the panel, the
display will be one of the following:
AUTOMATIC
INACTIVE
AUTOMATIC
ACTIVE
AUTOMATIC
PREALARM
If the point is disabled, the display will be one of the following. The Trouble Status field will
appear if the point is in trouble.
DISABLED
INACTIVE
<
Trouble Status>*
DISABLED
ACTIVE
<
Trouble Status>*
DISABLED
PREALARM
<
Trouble Status>*
If the point is in trouble, the display will read:
TROUBLE
INACTIVE
<
Trouble Status>*
TROUBLE
ACTIVE
<
Trouble Status>*
TROUBLE
PREALARM
<
Trouble Status>*
*The field
<
Trouble Status
>
will contain a device trouble message. Refer to this panel’s Operations
manual for information on these messages.
Line 7 - The custom label for this point
Line 8 - Continuation of the point’s custom label, first zone, and device type
Lines 9,10 - a display of all the zones that contain the current point being read.
Lines 11through 14 -These lines will have values in them only if the device is a detector. They will
not display for wireless detectors.
Line 11
V A L U E S
:
The screen displays the Alarm and Prealarm values that are in effect when read status is
requested. For example, if occupied settings are in effect, occupied values will display
1 2 1 % O F A L A R M
-
This field gives the detector reading as it relates to its
preprogrammed alarm level value (indicated in the next line on the screen). The example
above shows the detector exceeding the alarm level by 21%.
1 4 5 % O F P R E A L A R M
-
This field gives the detector reading as it relates to its
preprogrammed prealarm level value (indicated in the next line on the screen). The example
above shows the detector exceeding the prealarm level by 45%.
Point Control
Designation
Description
AUTOMATIC
The point is being controlled automatically by the panel.
DISABLED
The point has been forced into a disabled state by an outside source.
TROUBLE
The point is in a trouble state and is no longer functioning automatically.
Point Status
Designation
Description
INACTIVE
The point is currently reporting no events.
ACTIVE
The point is currently in an off-normal status.
PREALARM
The point is currently in a prealarm status.
www.PDF-Zoo.com
Summary of Contents for NFS-3030/E
Page 60: ...Program Autoprogram Menu 60 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Page 128: ...Type Codes FlashScan Codes 128 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Page 134: ...Glossary Glossary 134 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Page 142: ...NFS 3030 Programming Manual P N 51345 C 11 4 03 142 INDEX www PDF Zoo com...