Panel Program
Program
NFS-3030 Programming Manual P/N 51345:C 11/4/03
27
SOURCE:
Pressing this soft key will select the Source field and also toggle between display
formats if a point value is allowed. Enter a point or zone, or the panel’s node number if the mode
type is a system function such as acknowledge or reset.
Up to eight sources are allowed when
CONTROL
mode is chosen.
ACCEPT:
Press this soft key to save the changes to the point displayed. The next point address will
appear.
BACK:
Press this soft key to exit the screen without saving, and return to the ACS Programming
Screen.
3.2.8 Supervision
From the Panel Program Menu (1), select
SUPERVISION
to display the following screen.
Figure 3.12 Supervision Screen
Soft Keys
MAIN
POWER
SUPPLY
AC
FAIL
ADDRESS:
Press to enter the “Monitor AC Fail” (base plus
one) address of the main power supply. Refer to the main power supply manual for complete
addressing information. Type in the address using the keypad.
The LCD backlight will turn off when this power supply experiences AC failure (see
BACKLIGHT
in "LCD Programming" on page 23).
PRINTER:
Press to scroll through the types of printer supervision:
NONE
,
40-COLUMN
,
40-COLUMN
SUPERVISED
,
80-COLUMN
,
80-COLUMN
SUPERVISED
,
GRAPHIC
,
OR
GRAPHIC
SUPERVISED
. The printer will not be active if
NONE
is selected. If a
SUPERVISED
selection is made, the printer will be supervised. Default:
NONE
Note: When changing from an 80-column or 80-column supervised to a graphic or graphic
supervised printer (or vice-versa) , settings must be changed at the printer. Refer to this panel’s
installation manual for the settings.
AUXILIARY
TROUBLE
REPORTING:
Press to toggle between Yes and No. Choose Yes if a
trouble bus cable has been attached at J5 of the CPU-3030. Default: NO
TAMPER
INPUT:
Press the soft key to toggle between Yes, No, and AKS-1.
Yes/No reports (YES) or does not report (NO) a tamper situation at the panel cabinet door (as
determined by an STS-1 tamper switch connected as shown in this panel’s installation
manual).
AKS-1 should be selected when there is an AKS-1 key switch connected to the panel cabinet
door (which allows the operator to use Signal Silence, Reset, Drill and Acknowledge functions
when a key turns the lock to “Enable”). Default:
NO
S U P E R V I S I O N
M A I N P S A C F A I L A D D R E S S : L X X M X X X
P R I N T E R : 8 0 - C O L U M N
A U X I L I A R Y T R O U B L E R E P O R T I N G : N O
A C C E P T
T A M P E R I N P U T : N O
B A C K
www.PDF-Zoo.com
Summary of Contents for NFS-3030/E
Page 60: ...Program Autoprogram Menu 60 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Page 128: ...Type Codes FlashScan Codes 128 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Page 134: ...Glossary Glossary 134 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Page 142: ...NFS 3030 Programming Manual P N 51345 C 11 4 03 142 INDEX www PDF Zoo com...