Alter Status
Walk Test
66
NFS-3030 Programming Manual P/N 51345:C 11/4/03
Walk Test Activation Indications
FlashScan poll mode - Once the
START
TEST
soft key has been pressed:
•each intelligent addressable input device will blink its address in red, and each intelligent
addressable output device will blink its address in green. Pattern examples are given below.
•an input device activated in Walk Test latches on steady green for the duration of the test. If
the device is put in trouble (for instance, the detector head is removed, then replaced), the
LED will be latched on for the duration of the test.
•an output device activated in Basic Walk Test will remain active and the LED will glow
steady green for
- 4 seconds for alarms
- 8 seconds for troubles.
•an output device activated in Advanced Walk Test will remain active and the LED will glow
steady green until the
NEXT
TEST
soft key is pressed.
CLIP poll mode - Once the
START
TEST
soft key has been pressed:
•intelligent addressable input and output devices continue to blink red as usual until activated.
• an input device activated in Walk Test latches on steady red during activation. If the device is
put in trouble (for instance, the detector head is removed, then replaced), the LED wil be
latched on for the duration of the test.
•an output device activated during Basic Walk Test will remain active and the LED will glow
steady green (if a FlashScan module) or steady red (if a CLIP module) for
- 4 seconds for alarms
- 8 seconds for troubles.
•an output device activated in Advanced Walk Test will remain active and the LED will glow
steady green (if a FlashScan module) or steady red (if a CLIP module) until the
NEXT
TEST
soft key is pressed.
Conventional Devices - Monitor modules with the Type Codes
SMOKE CONV
,
HEAT DETECT
, and
SMOKE DETECT
, and outputs with the Type Code
FORM C RESET
do not participate in Walk Test
other than blinking their addresses if they are polled in FlashScan mode. To prevent the
occurrence of false alarms for conventional devices, 24 volt power will be interrupted for up to
a minute after Walk Test has been exited.
Figure 4.9 Walk Test Menu Screen
Address Blink Pattern
8
8 blinks, long stop, 8 blinks, long stop,....
37
3 blinks, stop, 7 blinks, long stop, 3 blinks, stop, 7 blinks, long stop,....
152
15 blinks, stop, 2 blinks, long stop, 15 blinks, stop, 2 blinks, long stop....
L A K E V I E W G E N E R A L H O S P I T A L
S Y S T E M N O R M A L
1 0 : 2 2 : 3 4 A
F R I J U L 1 9 , 2 0 0 2
W A L K T E S T
B A S I C / A D V A N C E D : A D V A N C E D
S I L E N T / A U D I B L E : A U D I B L E
P A R A M E T E R : L O O P S
A C C E P T
D I S A B L E A C S B O A R D S : Y E S
B A C K
www.PDF-Zoo.com
Summary of Contents for NFS-3030/E
Page 60: ...Program Autoprogram Menu 60 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Page 128: ...Type Codes FlashScan Codes 128 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Page 134: ...Glossary Glossary 134 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Page 142: ...NFS 3030 Programming Manual P N 51345 C 11 4 03 142 INDEX www PDF Zoo com...