Point Program
Program
NFS-3030 Programming Manual P/N 51345:C 11/4/03
47
Default:ULI
CROSS ZONE:
Press to scroll through the selection list of YES, NO, ZONE, HEAT. Default: NO.
SOAK TIME:
Press to type a value from 0 to 9999 (seconds). Default: 0000
3.4.6 Logic Zone
Logic Zone Programming
This screen displays when a logic zone is entered at the Point Programming Menu (see Figure 3.22
on page 34 ).
The logic equation for that zone will display in line 6. Line 4 indicates the current state of the logic
zone (ON or OFF). If there is no equation at the logic zone number entered, nothing will display in
lines 4 and 6, and the user must press the
EDIT EQUATION
soft key to proceed to the next screen
and enter an equation.
Refer to Appendix E: CBE: Zones and Equations for information on how to create a logic equation,
and how logic equations operate.
Figure 3.38 Logic Zone Programming Menu Screen
Soft Keys
EDIT EQUATION:
Press to proceed to the edit screen to add or edit a logic equation.
NEXT/PREVIOUS EQUATION:
Press to view the next or previous logic equation.
Edit Logic Equation
This screen displays when the
EDIT EQUATION
soft key is pressed on the Logic Zone.
L O G I C Z O N E P R O G R A M M I N G M E N U
L O G I C Z O N E
Z L x x x x
A U T O M A T I C O F F
A N D ( Z 2 0 , O R ( L 2 D 1 5 9 , L 2 D 1 4 ) )
E D I T E Q U A T I O N
N E X T E Q U A T I O N
A C C E P T
P R E V I O U S E Q U A T I O N
B A C K
www.PDF-Zoo.com
Summary of Contents for NFS-3030/E
Page 60: ...Program Autoprogram Menu 60 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Page 128: ...Type Codes FlashScan Codes 128 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Page 134: ...Glossary Glossary 134 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Page 142: ...NFS 3030 Programming Manual P N 51345 C 11 4 03 142 INDEX www PDF Zoo com...