System Troubles
130
NFS-3030 Programming Manual P/N 51345:C 11/4/03
Appendix Table H-2 gives a description of each system trouble.
Appendix Table H-2 System Trouble Descriptions
SYSTEM TROUBLES
TROUBLE MESSAGE TYPE
TROUBLE DESCRIPTION
ADV WALK TEST
There is an Advanced Walk Test in progress.
ANNUN x NO ANSWER
The annunciator at address x is not responding.
ANNUN x TROUBLE
The annunciator at address x is in trouble.
AUXILIARY TROUBLE
Auxiliary device connected to the CPU-3030 at J5 is in trouble or the cable is missing.
BASIC WALK TEST
A Basic Walk Test is in progress.
CORRUPT LOGIC EQUAT
The database that houses the panel’s logic equations is corrupt. It must be re-downloaded, or
all programming must be cleared and re-entered.
DRILL INITIATED
Drill has been initiated locally.
DRILL RECEIVED
Drill has been initiated remotely.
EPROM ERROR
The application and/or boot code is corrupt. Service required.
EXTERNAL RAM ERROR
The external RAM test failed. Service required.
GROUND FAULT
A ground fault has occurred within the panel.
GROUND FAULT LOOP x
There is a ground fault on loop x.
INTERNAL RAM ERROR
The internal RAM test failed. Service required.
LOADING.NO SERVICE
A program or database download is in progress. The panel is NOT providing fire protection
during the download. Proper authorities should be notified while a download is in progress so
that other means of fire protection can be supplied.
LOOP x- x COMM FAILURE
Loops x and x are not responding. The LCM and LEM for those loops must be serviced.
MAN EVAC INITIATED
Local initiation of DRILL
MAN EVAC RECEIVED
Network initiation of DRILL
MANUAL MODE ENTERED
An annunciator has been placed in manual mode.
NCM COMM LOSS
Communication lost between CPU-3030 and NCM
NETWORK FAIL PORT x
Communication lost between NCM Port x and corresponding node.
NETWORK INCOMPATIBILITY
The brand of this panel is incompatible with this network.
NFPA 24HR REMINDER
This message occurs every day at 11 am if any troubles exist.
NVRAM BATT TROUBLE
Battery backup and/or clock backup is low. Replace battery.
NO DEV. INST ON L1
No devices are installed on the system.
NO POWER SUPPLY INST
The address of the main power supply has not been entered.
PANEL DOOR OPEN
The panel door is open.
PRINTER OFF LINE
Communication loss with printer. Restore power and/or printer’s online status.
PRINTER PAPER OUT
Add paper.
PROGRAM CORRUPTED
The database that houses the panel’s programming is corrupt. It must be re-downloaded, or
all programming must be cleared and re-entered. Service required.
PROG MODE ACTIVATED
A user is currently using the panel’s programming menus.
REMOTE DISPLAY x NO ANSWER
The remote display at address x is not responding.
REMOTE DISPLAY x TROUBLE
The remote display at address x is in trouble.
SELF TEST FAILED
Diagnostic test failed. Service required.
SOFTWARE MISMATCH
One or more LCM software revisions do not match other LCMs, and/or the NCM is not
network version 5.0, or LCD-160 software is incompatible.
STYLE 4 SHORT x LOOP x
Service required.
STYLE 6 POS. LOOP x
There is a short circuit on the positive side of loop x. Style 6 and Style 7 are supervised
methods of communicating with addressable devices. If the control panel detects a trouble
(open or short), it will drive both ends of the loop, maintaining communication in an
unsupervised method. The latching trouble will display on the panel as a Style 6 trouble until
you correct the condition and press reset. Style 7 configuration of the SLC requires the use of
ISO-X modules.
STYLE 6 NEG. LOOP x
There is a short circuit on the negative side of loop x. Style 6 and Style 7 are supervised
methods of communicating with addressable devices. If the control panel detects a trouble
(open or short), it will drive both ends of the loop, maintaining communication in an
unsupervised method. The latching trouble will display on the panel as a Style 6 trouble until
you correct the condition and press reset. Style 7 configuration of the SLC requires the use of
ISO-X modules.
STYLE 6 SHORT LOOP x
Style 6 and Style 7 are supervised methods of communicating with addressable devices. If the
control panel detects a trouble (open or short), it will drive both ends of the loop, maintaining
communication in an unsupervised method. The latching trouble will display on the panel as a
Style 6 trouble until you correct the condition and press reset. Style 7 configuration of the SLC
requires the use of ISO-X modules.
SYSTEM INITIALIZATION
One or more devices (detectors or modules) can not report activation. This can occur
following system startup, when exiting Walk Test, or following a device trouble of No
Response.
www.PDF-Zoo.com
Summary of Contents for NFS-3030/E
Page 60: ...Program Autoprogram Menu 60 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Page 128: ...Type Codes FlashScan Codes 128 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Page 134: ...Glossary Glossary 134 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Page 142: ...NFS 3030 Programming Manual P N 51345 C 11 4 03 142 INDEX www PDF Zoo com...