q
GENERAL RELAIS
: Trouble Relais, Alarm Relais and Siren Relais.
q
EXTERNAL RELAIS
: 16-Relay optional board.
q
DOUBLE THRESHOLD ZONE
: by means of this programming the following signals will be displayed in
case of detector alarm: only one detector in alarm= zone in prealarm condition; two or more detectors in
alarm= zone in alarm condition.
q
ENABLING THE INHIBITION OF THE MANUAL RELEASE INPUT
: the operator can avoid that the control
panel consider the status of the inhibiton input of the single release channels. In this case the manual relea-
se input activation is always allowed and it will activate the release channel.
LOGICAL DIAGRAM
»
NOTE: In “Battery trouble condition” the release NEVER occurs.
CFP-600-Gloss-E.VP
Installation and Operating Manual
Page 28
Doc. M.131.1-CFP600-ENG
Rev. B.1
NOTIFIER ITALIA
MANUAL RELEASE
INPUT
AUTOMATIC RELEASE FOR TWO
ZONES IN ALARM CONDITION
PROGRAMMING THE
INHIBITION INPUT ENABLING
INHIBITION
INPUT
RELEASE
ACTIVATED
DO NOT CARE
DISABLED
DO NOT CARE
YES
DO NOT CARE
DO NOT CARE
ACTIVATED
ACTIVATED
DISABLED
DISABLED
= NOT INHIBITED
= INHIBITED
YES
NO
ACTIVATED
ACTIVATED
DO NOT CARE
DO NOT CARE
ENABLED
ENABLED
= NOT INHIBITED
= INHIBITED
YES
NO
DO NOT CARE
DO NOT CARE
ACTIVATED
ACTIVATED
DO NOT CARE
DO NOT CARE
= NOT INHIBITED
= INHIBITED
YES
NO
MANUAL RELEASE
AUTOMATIC RELEASE
INHIBITION INPUT
DISABLED
INHIBITION INPUT
INHIBITION INPUT
ENABLED
RELEASE