CHANGE PREALARM RECOGNITION TIME (Level 3 Password required)
Press ENTER to display as follows.
Press ENTER to change the Recognition Time.
Use CURSOR keys to program the new Recognition Time.
Then, press ENTER to confirm.
»
NOTE : by pressing the control signal silence key, the operator, in case of prealarm, may start the Recogni-
tion Time. This time allows the operator to carry out a system recognition to verify the real presence of fire.
If the Recognition time expires before performing a reset the control panel will activate alarm signals.
For further details see Appendix A: Day/Night Operation.
Values admitted are: 1 minute to 19, 59
NOTE: enter the Level 3 PASSWORD to display the Recognition Time.
ALARM COUNTER
By pressing ENTER key the display will show a screen as follows, in-
dicating the number of alarm events.
NOTE: the alarm event max number is equals to 9999
By pressing ENTER key the operator may clear the counter only if he
knows the Level 4 password
CHANGE DATE/TIME (Level 3 Password required)
Use ENTER key and CURSOR KEYS to program date and time.
»
NOTE: enter the Level 3 PASSWORD to program date and time.
Page 6
Installation and Operating Manual
CFP-600-Prog-2.VP
NOTIFIER ITALIA
Rev. B.1
Doc. M-131.1-CFP600-ENG
USER MODE
| A08
RECOGN. TIME | G08
| D00
| E00
LEV.3 PASSW. |
|
|
|
USER MODE
| A08
RECOGN. TIME | G08
10'00''05'00''| D00
| E00
Time
Date
USER MODE
| A00
DATE/TIME
| G00
| D00
01-01-97 00:48| E00
USER MODE
| A00
ALARM COUNTER | G00
| D00
| E00
ALARM COUNTER | A00
10
| G00
| D00
Modify
Exit | E00