CFP-600-E
Control Panel Wiring
1
15
EXTERNAL N.O. SILENCE PUSH BUTTON
220 VAC MAINS
MAINS FILTER
MAINS
FUSE
5 x 20 1 A
CNA
EXTERNAL N.O. RESET PUSH BUTTON
+Z.12
GND
+Z11
+Z10
GND
+Z.9
+Z.8
GND
+Z.7
+Z.6
GND
+Z.5
+Z.4
GND
+Z.3
+Z.2
GND
+Z.1
2 X BATTERIES ( 12V , 6Ah Max.)
24V Ancillary device Fuse (1AT)
Battery Fuse (3,15AF)
External Sirens
1AT FUSE
FLAT CABLE to :
16-Relay Board
2-Release channel Board
4 3
F3
2 1
F1
F2
TRANSFORMER
External Power Supply Input
24 VDC Nominals
1
3
NO*
C
NC
C
NO
NC
C
NO
NC
-
+
1
10
Watch-Dog Enabling
DO NOT TAMPER
W-1
PROG
OFF
W-3
OFF
ON
CPU Reset
TROUBLE
PREALARM
ALARM
SIRENS
W1=PROG - Programming Enabling
W1=OFF - Disabled Programming
SIREN
BELL
W-2
SIREN CONNECTION TYPE
W2=SIREN - EOL Res.2K7- Check SHORT C. and OPEN C.
W2=BELL - Diode - Check OPEN CIRCUITt
CPU Reset = Panel uP Reset
WD Reset = WD Trouble Reset (it turns off the WD-CPU TRB Led)
5
1
-
+
2.7K
1/4W
Polarized
Electronic SIREN
SUPERVISED
WD
Reset
Keyboard key
24V RESETTABLE OUTPUT for ancillary devices
24V NOT RESETTABLE OUTPUT for ancillary devices
18
2.7K
1/4W
1 K
1/2W
N.O.
Conventional Detector with relay output
or Push Button N.O.
Conventional Detector
2451 - 5451 - 1451
2.7K
1/4W
+
2
3
4
1
-
2
3
4
1
LED Indicator
LED Indicator
2 Threshold Zone detector wiring:
Connect a 560 Ohm 1/2 W EOL resistor each detector
2.7K
1/4W
560 Ohm
1/2 W
560 Ohm
1/2 W
+
2
3
4
1
-
2
3
4
1
BELL
DIODE
5
8 7 6
1
4 3 2
M4
Receiver 6424
N.O.
Alarm Contact
Transmitter 6424
1 K
1/2 W
2.7K
1/4W
Doc.M-131.1-CFP600-ENG
Installation and Operating Manual
NOTIFIER ITALIA
CFP-600-Cablrv21-E.cdr
Rev. B.1
Page 23
+
-
+
-
+
-
+
-
+
-
+
-
+
-