Automatic Release Channel Management
Page 20
Installation and Operating Manual
CFP-600-Prog-5.VP
NOTIFIER ITALIA
Rev. B.1
Doc. M-131.1-CFP600-ENG
YES
NO
NO
NO
FIRST ALARM
PREALARM LED= FLASHING
PREALARM RELAY= ON
BUZZER= STEADY SOUND
INHIBITION?
RELEASE INHIBITION LED= FLASHING
SIGNAL SILENCE?
PREALARM LED= ON
PREALARM RELAY= OFF
BUZZER= intermittent sound
Release Inhibition LED=Flashing
Silenced control LED= ON
SECOND ALARM
ALARM LED= Flashing
ALARM RELAY= ON
SOUNDER RELAY= ON
EVACUATION RELAY= ON
EVACUATION LED= ON
BUZZER= Steady sound
Release Inhibition LED=Flashing
RELEASE INHIBITED
WAITING FOR RESET
SIGNAL SILENCE?
PREALARM LED= ON
PREALARM RELAY= OFF
BUZZER= Intermittent sound
SILENCED CONTROL LED= ON
Second alarm
Wait Time
= Expired?
SECOND ALARM
ALARM LED= FLASHING
ALARM RELAY= ON
SOUNDER RELAY= ON
EVACUATION RELAY= ON
EVACUATION LED= ON
BUZZER= STEADY SOUNDER
Detector Line Automatic RESET
Prealarm LED= OFF
Prealarm RELAY= OFF
Silenced Control LED= OFF
BUZZER= OFF
WAITING FOR RESET
SIGNAL SILENCE?
ALARM RELAY= OFF
SOUNDER RELAY= OFF
SILENCED CONTROL LED= ON
BUZZER= INTERMITTENT SOUNDER
EVACUATION TIME
= EXPIRED?
Release Actuation
Release LED= ON
PRESSURE-METER ACTIVATED?
RELEASE ACTUATION
RELEASE ACTUATION= 3?
TROUBLE LED= FLASHING
TROUBLE RELAY= ON
BUZZER= INTERMITTENT SOUND
WAITING FOR RESET
EVACUATION 1 LED= ON
RELEASE 1 LED= ON
RELEASE 1 TROUBLE LED= FLASHING
TROUBLE RELAY= ON
TROUBLE LED= ON
BUZZER= INTERMITTENT SOUND
YES
NO
NO
YES
YES
YES
NO
NOTE:ZONE ALARM
Single threshold Zone:
First Alarm= Zone in Alarm status
Double threshold Zone:
First Alarm= Zone in Prealarm status
Second Alarm= Zone in Alarm status
»
NOTE: In “battery trouble” condition
the release never occurs.