Nordyne iQDrive Installation Instructions Manual Download Page 9

9

Under normal circumstances it is not necessary or advisable 
to change these from their default values.

Heat Off Delay

If the system includes a G6 gas furnace, you may use the   
or 

 keys to select HEAT OFF DELAY.  Press the   key to 

enter the screen which allows changes to the length of time 
that the blower (indoor fan) will remain on after the furnace 
fl ame is extinguished.  Under normal circumstances it is not 
necessary or advisable to change this from its default value 
of 120 seconds.

Altitude Adjust

If the system includes an iQ modulating gas furnace, you 
may use the   or   keys to select ALTITUDE ADJUST. 

 

Press the   key to enter the screen which allows changes to 
the installation altitude (feet above sea level).  This entry is 
advisable for the modulating gas furnace.  Refer also to the 
furnace Installation Instructions.

Service Tests

You may use the   or   keys to select SERVICE TESTS.  
Press the   key to enter the screen which allows access to 
a list of service tests.  These tests provide an easy way for 
the service person to operate the system in various modes 
for operational confi rmation and diagnostic troubleshooting 
during installation startup.  The following fi ve options are 
available in the submenu.

S E R V I C E   T E S T S

C H A R G E   M O D E

A I R   C O N D   R U N   T E S T S

F U R N A C E   T E S T S





H E AT   P U M P   R U N   T E S T S

D I S C R E T E   O U T P U T S

NOTE: While running the system from Service Tests is 
convenient for some startup operations, much of the normal 
fault handling and diagnostic message functionality is disabled.

Within each test screen there may be more than one entry which 
can be changed.  Select the desired entry to be modifi ed using 
the   and   keys.  The line or value with a dark background 
behind the characters is considered “selected”.  Press the   
key to allow changing the selected item (its dark background 
will then blink).  Set the desired value for the item using the 

 and   keys, then press the   key to save it.

The following is a brief description of the SERVICE TEST 
categories. NOTE: With iQ Zone systems there may be a delay 
before the test begins, as all zone dampers open.

CHARGE MODE – Runs the system at the proper speed for 
checking and adjusting refrigerant charge.  Select the mode as 
HEATING or COOLING, then change RUN from OFF to ON.  
The screen backlight will blink red.  The user may navigate 
to other screens (e.g., SERVICE INFORMATION) during the 
process until ON in the CHARGE MODE screen is changed 
back to OFF and saved.  The red blinking backlight serves as 
a reminder that the unit is operating in an abnormal (service) 
mode.  Select OFF (from the list that includes ON and OFF) 
and SAVE ( ) when fi nished.

FURNACE TESTS – Runs the system at the selected fi re 
level to allow confi rmation of proper operation.  The screen 
backlight will blink red.  A short list of instructions (reminders) 
is provided. Select START to run a single stage furnace. Select 
LO FIRE or HI FIRE to run a two stage furnace. The user may 
navigate to other screens (e.g., SERVICE INFORMATION) 
during the process.  The red blinking backlight serves as a 
reminder that the unit is operating in an abnormal (service) 
mode.  Select DONE (from the list that includes LO FIRE, HI 
FIRE, START, STOP) and SAVE ( ) when the test is complete, 
before leaving the screen for the last time.

AIR COND RUN TESTS and HEAT PUMP RUN TESTS – In 
these screens the unit can be made to run at a fi xed speed 
regardless of room temperature.  RUN can be changed 
between OFF, MAX (speed), INTERMED(iate speed), and 
MIN (speed).  MAX speed is the same as that used in charge 
mode.  The screen backlight will blink red when anything but 
OFF is selected and saved. The user may navigate to other 
screens (e.g., SERVICE INFORMATION) during the process 
until RUN in this screen is changed back to OFF and saved.  
The red blinking backlight serves as a reminder that the unit 
is operating in an abnormal (service) mode. This screen is 
primarily intended for test agency usage. Heat pump run 
tests apply only to heat pump units. Select OFF and SAVE 
( ) when fi nished.

For iQ heat pumps the capability to force a defrost is available.  
As indicated on the HEAT PUMP RUN TESTS screen, this 
feature may only be used when MAX speed has been selected.  
To perform a sample defrost while a MAX speed heating run 
test is running, press the   key to select DEFROST NOW, then 
press the ( ) key to begin the defrost. The defrost sequence 
will proceed, including use of auxiliary heat while heating the 
coil and the 8 minute post-defrost coil temperature calibration.  
Only use this feature if the outdoor conditions are typical 
heating conditions. Do not force a defrost before the system 
has operated in heating for several minutes fi rst.

DISCRETE OUTPUTS – When the unit is off, this screen 
allows the user to operate certain relay-driven outputs in the 
system for diagnostic purposes: humidifi er (on the indoor 
interface board or blower control board), reversing valve (on 
the outdoor interface board), indoor coil EXV (on the indoor 
interface board or blower control board), outdoor coil EXV (on 
the outdoor interface board), and crankcase heater (on the 
outdoor interface board).  More than one of these can be set 
to ON at the same time.  Leaving the DISCRETE OUTPUTS 
screen will shut all of the listed outputs off.

Summary of Contents for iQDrive

Page 1: ...electronic air cleaners and U V ultraviolet sterilizing lamps Refer to the System Operation section below for a complete description of how to use the various features of the system In addition to pr...

Page 2: ...ORMATION Screens 10 Other Configuration Entries 11 Minimum Heat Pump Operating Temp 11 Auto Changeover Time 12 Date and Time 12 Program Schedule vs Nonprogrammable 12 Dehumidification 12 Humidity Sett...

Page 3: ...pment Consult local building codes for rooftop installations After a location has tentatively been selected trace routing of new or pre existing refrigerant lines two and power and control wiring See...

Page 4: ...lace the control panel cover before applying power IMPORTANT It is critical that the wires meant to connect to 24 vaccontrolpower RED GRAY arenotmistakenly connected to the communication bus wires YEL...

Page 5: ...frigerant gauge manifold to both the vapor and liquid service valves See Figure 8 Connect the center port to the vacuum pump 2 Open both manifold valves and start the vacuum pump After a short time it...

Page 6: ...ervice valve and suction service port located at the left side of the access panel above the liquid service valve See Figure 8 2 Start the system in CHARGE MODE HEATING Allow the system to run 15 minu...

Page 7: ...ew thermostat or moving a thermostat to a different type of iQ system The outdoor unit should be powered up when confirming or entering system configuration With the first line SYSTEM CONFIGURATION se...

Page 8: ...king changes or entries under ACCESSORIES is optional Dealer Information Usethe or keystoselectDEALERINFORMATION Press the key to enter the dealer information summary screen and submenus and screens T...

Page 9: ...der that the unit is operating in an abnormal service mode Select OFF from the list that includes ON and OFF and SAVE when finished FURNACE TESTS Runs the system at the selected fire level to allow co...

Page 10: ...MODEL NUMBER 20 2 tons 30 3 tons etc With correct configuration only 20 30 or 40 should appear here LOW PRESSURE SW shows the state of the low pressure switch Any COMPR ERROR CODE number normally 0 w...

Page 11: ...s helpful system status messages including whether or not the system is dehumidifying during cooling H E A T P U M P H E A T I N G U S E D D E M A N D S P 7 0 0 COMP RPM R O O M T E M P A C T S T E P...

Page 12: ...from having to do it but provides an accurate time and date stamp for any faults logged during installation checkout for example in FAULT HISTORY By default the clock is in 12 hour format This may be...

Page 13: ...The humidify setpoint can be set in the range 30 to 45 in increments of 5 The dehumidify setpoint can be set in the range 35 to 70 in increments of 5 Press the key to save any changes 5 Press the key...

Page 14: ...deliver air to all zones when not heating or cooling set the Fan Mode to ON The Intermittent Fan featuredescribedearlierwillalsooperate servingallzones Refer to the iQ Drive User s Manual for other de...

Page 15: ...u the iQ controller has never communicated with the zone control board and power and communication wiring to the zone control board need to be checked If the main screen reverts to back to the zoning...

Page 16: ...ELECTRIC SHOCK HAZARD Disconnect power before servicing the outdoor unit Failure to follow these instructions may result in electric shock or death Trouble shooting the outdoor unit may require that p...

Page 17: ...om the interface board Check for 24 vac between R and C on the interface board and check that the tabs marked R and C on the interface board are wired to R and C on the EXV board These should not be c...

Page 18: ...verse There is a configurable delay Auto Changeover Time between operating in heating and restarting in cooling or the reverse when in AUTO mode The default delay for this changeover is 60 minutes Abn...

Page 19: ...changes processed until zone dampers have completed any prior operation For example an extra minute delay is deliberately included when one or more zones are closed MAINTENANCE IMPORTANT Be certain t...

Page 20: ...20 Figure 3 iQ Drive Heat Pump Control Panel Inverter black plastic case Outdoor Interface Board Low Voltage Control Wiring Compartment Contactor Outdoor EXV Board...

Page 21: ...ER EXV REACTOR T2 T1 L1 L2 NO C A B CCH RELAY REVERSING VALVE COIL OUTDOOR AMBIENT TEMP SENSOR COMPR DISCHG TEMP SENSOR LOW PRESSURE SWITCH OD FAN MOTOR SUCTION LINE THERMISTOR 2X FIELD WIRING TO INDO...

Page 22: ...22 Figure 5 Low Voltage Compartment Control Wiring Connections GRN GND DX DX WHT YEL RED GRY C R Figure 6 iQ Heat Pump Control Wiring Outdoor Destinations...

Page 23: ...23 Figure 7 Wire Looping Through a Toroidial Choke SINGLE LOOP SHOWN Figure 8 Service Ports and Valves Below Control Panel Suction Service Port Vapor Line Service Valve Liquid Line Service Valve...

Page 24: ...efrigerantif above the curve AddRefrigerantif belowthe curve 3 Ton 2 Ton 4 Ton 240 260 280 300 320 340 360 380 75 80 85 90 95 100 105 110 115 Liquid Pressure psig Liquid Temperature F Heating Mode Out...

Page 25: ...HEAT PUMP USAGE LIMIT BACKUP HEAT RESPONSE OFFSETS INDOOR TEMPERATURE REMOTE INDOOR TEMP RELATIVE HUMIDITY HEAT ANTICIPATOR SCREEN SETTINGS FAHRENHEIT OR CELSIUS 12 OR 24 HOUR CLOCK CONTRAST INTERMITT...

Page 26: ...R PHONE SELECT BRAND NAME MODEL NUMBER CONTRACTOR NAME CONTRACTOR PHONE ACCESSORIES AIR FILTER HUMIDIFIER UV LAMP AIR CLEANER AIR FILTER CHANGE HUMIDIFIER CHANGE UV LAMP CHANGE AIR CLEANER CHANGE SERV...

Page 27: ...on Behind Interface Board to the left of blue DIP switch block Figure 13 Interface Board LED Locations Inverter LED to the left of blue DIP switch block Communication LED DEF CCH Y RV Figure 14 EXV Bo...

Page 28: ...NS WITH THE OWNER 708921 Specifications illustrations subject to change without notice or incurring obligations O Fallon MO Printed in U S A 09 10 Power Plug Red Power LED iQ Comm LED s Zone Network L...

Reviews: