Nordyne iQDrive Installation Instructions Manual Download Page 13

13

1. From the Main Screen, press the   or   key to select 

MENU at the bottom of the screen, then press the   key 
to see the Main Menu.

2. Use the   or   key to select SETTINGS, then press the 

 key to enter the Settings menu.

3. Use the   or   key to select OPTIONS, then press the   

key to enter the Options screen.

4. Use  the 

 or 

 key to select the value under 

DEHUMIDIFICATION, then press the   key to allow 
changing the setting.

5. Use the   or   key to change the value between “ON” 

(the default) and “OFF”, then press the   key to save the 
setting.

6. Press the   key multiple times to return to the Main Screen.

Humidity Settings

Separate setpoints for humidifi cation and dehumidifi cation are 
available in units of percent RH (relative humidity).  The humidify 
setpoint only is relevant if optional humidifi er equipment has 
been installed and connected to the system (the 24 vac 
“H” output – See the Field Wiring Installation Instructions).  
The installer should clarify for the homeowner that priority 
is given to cooling over dehumidifying, so the ability of the 
system to satisfy the RH setpoint(s) depends on a variety of 
conditions.  For example if the cooling load causes the unit 
to run at an intermediate speed or higher, the effectiveness 
of dehumidifi cation is increased.

Humidifi cation can operate when the system is heating 
or the fan is set to Manual (ON) with the compressor off.  
Dehumidifi cation can operate only when the system is 
cooling mode, the dehumidifi cation option is enabled, and 
room temperature is close to the setpoint.

 

To set the humidity 

setpoint(s), perform the following:

1.  From the Main Screen, press the   or   key to select RH 

at the bottom of the screen, then press the   key to see 
the Humidity screen. The current setpoints are displayed.

2.  As indicated at the bottom of the screen, press the   key 

to enter the Humidity Settings screen.

H U M I D I T Y   S E T T I N G S

4 5 %

H U M I D I F Y

D E H U M I D I F Y







5 0 %

3. Use the   or   key to select the RH setting to change, 

then press the   key to allow changes.

4. Use the   or   key to change the RH setting then press 

the   key to save the setting.  The confi gurable ranges for 

HUMIDIFY and DEHUMIDIFY are different, and changing 
one may push the other so that a minimum of 5% is 
maintained between the settings. The humidify setpoint 
can be set in the range 30 to 45% in increments of 5%. The 
dehumidify setpoint can be set in the range 35 to 70% in 
increments of 5%.  Press the   key to save any changes

5. Press the   key multiple times to return to the Main Screen.

Smart Recovery

When Smart Recovery is enabled, the system will start 
changing the cooling or heating setpoint in advance of a 
schedule change so that the room temperature is at or near 
the setpoint of the subsequent schedule time block when that 
time block begins. It only applies if the subsequent cooling 
setpoint is lower or heating setpoint in higher. Also, if PROGRAM 
SCHED USAGE is set to NON PROGRAMMABLE, this option 
does not apply. To change the smart recovery option, perform 
the following:

1. From the Main Screen, press the   or   key to select 

MENU at the bottom of the screen, then press the   key 
to see the Main Menu.

2. Use the   or   key to select SETTINGS, then press the 

 key to enter the Settings menu.

3. Use the   or   key to select OPTIONS, then press the   

key to enter the Options screen.

4. Use the   or   key to select the value under SMART 

RECOVERY, then press the   key to allow changing the 
setting.

5. Use the   or   key to change the value between “OFF” 

(the default) and “ON”, then press the   key to save the 
setting.

6. Press the   key multiple times to return to the Main Screen.

Zone Control

The installer should provide to the homeowner(s) a document 
or diagram which lists or shows (a) the rooms assigned to 
each zone number, (b) the weighting assigned to each zone, 
(c) the zone module number associated with each supply vent.

Current date and time must be set in the iQ thermostat/controller 
since they will be transmitted to, and continually updated in 
the local zone thermostats. The Security Lockout feature will 
not prevent changing settings in local zone thermostats in an 
iQ Zone system.

Temperature units (Fahrenheit or Celsius) can be changed 
as follows: Locate the set of eight microswitches on the iQ 
Zone main circuit board. Disconnect control power from the 
circuit board. Set microswitch #6 up (on) for °F, down (off) for 
°C. Reconnect control power.

It is recommended for the installer to instruct the homeowner(s) 
on the following:

For zoning operation, Operating Mode (COOL, HEAT, 
AUTO, E-HEAT, or OFF) must be selected from the iQ Drive 
thermostat/controller as with non-zoning systems.  However, 
the temperature setpoints that will be used are entered and 
stored at the local zone thermostats.  With iQ Zone systems, 

Summary of Contents for iQDrive

Page 1: ...electronic air cleaners and U V ultraviolet sterilizing lamps Refer to the System Operation section below for a complete description of how to use the various features of the system In addition to pr...

Page 2: ...ORMATION Screens 10 Other Configuration Entries 11 Minimum Heat Pump Operating Temp 11 Auto Changeover Time 12 Date and Time 12 Program Schedule vs Nonprogrammable 12 Dehumidification 12 Humidity Sett...

Page 3: ...pment Consult local building codes for rooftop installations After a location has tentatively been selected trace routing of new or pre existing refrigerant lines two and power and control wiring See...

Page 4: ...lace the control panel cover before applying power IMPORTANT It is critical that the wires meant to connect to 24 vaccontrolpower RED GRAY arenotmistakenly connected to the communication bus wires YEL...

Page 5: ...frigerant gauge manifold to both the vapor and liquid service valves See Figure 8 Connect the center port to the vacuum pump 2 Open both manifold valves and start the vacuum pump After a short time it...

Page 6: ...ervice valve and suction service port located at the left side of the access panel above the liquid service valve See Figure 8 2 Start the system in CHARGE MODE HEATING Allow the system to run 15 minu...

Page 7: ...ew thermostat or moving a thermostat to a different type of iQ system The outdoor unit should be powered up when confirming or entering system configuration With the first line SYSTEM CONFIGURATION se...

Page 8: ...king changes or entries under ACCESSORIES is optional Dealer Information Usethe or keystoselectDEALERINFORMATION Press the key to enter the dealer information summary screen and submenus and screens T...

Page 9: ...der that the unit is operating in an abnormal service mode Select OFF from the list that includes ON and OFF and SAVE when finished FURNACE TESTS Runs the system at the selected fire level to allow co...

Page 10: ...MODEL NUMBER 20 2 tons 30 3 tons etc With correct configuration only 20 30 or 40 should appear here LOW PRESSURE SW shows the state of the low pressure switch Any COMPR ERROR CODE number normally 0 w...

Page 11: ...s helpful system status messages including whether or not the system is dehumidifying during cooling H E A T P U M P H E A T I N G U S E D D E M A N D S P 7 0 0 COMP RPM R O O M T E M P A C T S T E P...

Page 12: ...from having to do it but provides an accurate time and date stamp for any faults logged during installation checkout for example in FAULT HISTORY By default the clock is in 12 hour format This may be...

Page 13: ...The humidify setpoint can be set in the range 30 to 45 in increments of 5 The dehumidify setpoint can be set in the range 35 to 70 in increments of 5 Press the key to save any changes 5 Press the key...

Page 14: ...deliver air to all zones when not heating or cooling set the Fan Mode to ON The Intermittent Fan featuredescribedearlierwillalsooperate servingallzones Refer to the iQ Drive User s Manual for other de...

Page 15: ...u the iQ controller has never communicated with the zone control board and power and communication wiring to the zone control board need to be checked If the main screen reverts to back to the zoning...

Page 16: ...ELECTRIC SHOCK HAZARD Disconnect power before servicing the outdoor unit Failure to follow these instructions may result in electric shock or death Trouble shooting the outdoor unit may require that p...

Page 17: ...om the interface board Check for 24 vac between R and C on the interface board and check that the tabs marked R and C on the interface board are wired to R and C on the EXV board These should not be c...

Page 18: ...verse There is a configurable delay Auto Changeover Time between operating in heating and restarting in cooling or the reverse when in AUTO mode The default delay for this changeover is 60 minutes Abn...

Page 19: ...changes processed until zone dampers have completed any prior operation For example an extra minute delay is deliberately included when one or more zones are closed MAINTENANCE IMPORTANT Be certain t...

Page 20: ...20 Figure 3 iQ Drive Heat Pump Control Panel Inverter black plastic case Outdoor Interface Board Low Voltage Control Wiring Compartment Contactor Outdoor EXV Board...

Page 21: ...ER EXV REACTOR T2 T1 L1 L2 NO C A B CCH RELAY REVERSING VALVE COIL OUTDOOR AMBIENT TEMP SENSOR COMPR DISCHG TEMP SENSOR LOW PRESSURE SWITCH OD FAN MOTOR SUCTION LINE THERMISTOR 2X FIELD WIRING TO INDO...

Page 22: ...22 Figure 5 Low Voltage Compartment Control Wiring Connections GRN GND DX DX WHT YEL RED GRY C R Figure 6 iQ Heat Pump Control Wiring Outdoor Destinations...

Page 23: ...23 Figure 7 Wire Looping Through a Toroidial Choke SINGLE LOOP SHOWN Figure 8 Service Ports and Valves Below Control Panel Suction Service Port Vapor Line Service Valve Liquid Line Service Valve...

Page 24: ...efrigerantif above the curve AddRefrigerantif belowthe curve 3 Ton 2 Ton 4 Ton 240 260 280 300 320 340 360 380 75 80 85 90 95 100 105 110 115 Liquid Pressure psig Liquid Temperature F Heating Mode Out...

Page 25: ...HEAT PUMP USAGE LIMIT BACKUP HEAT RESPONSE OFFSETS INDOOR TEMPERATURE REMOTE INDOOR TEMP RELATIVE HUMIDITY HEAT ANTICIPATOR SCREEN SETTINGS FAHRENHEIT OR CELSIUS 12 OR 24 HOUR CLOCK CONTRAST INTERMITT...

Page 26: ...R PHONE SELECT BRAND NAME MODEL NUMBER CONTRACTOR NAME CONTRACTOR PHONE ACCESSORIES AIR FILTER HUMIDIFIER UV LAMP AIR CLEANER AIR FILTER CHANGE HUMIDIFIER CHANGE UV LAMP CHANGE AIR CLEANER CHANGE SERV...

Page 27: ...on Behind Interface Board to the left of blue DIP switch block Figure 13 Interface Board LED Locations Inverter LED to the left of blue DIP switch block Communication LED DEF CCH Y RV Figure 14 EXV Bo...

Page 28: ...NS WITH THE OWNER 708921 Specifications illustrations subject to change without notice or incurring obligations O Fallon MO Printed in U S A 09 10 Power Plug Red Power LED iQ Comm LED s Zone Network L...

Reviews: