Nordyne iQDrive Installation Instructions Manual Download Page 15

15

5.  For systems without iQ Zone, adjust the operating setpoint 

if desired using a temporary hold (pressing the   or   key 
when the Main Screen is displayed). With iQ Zone, zone 
control enabled, adjust the operating setpoint for each zone 
individually by touching the   or   icon.  (Refer to iQ Zone 
System Zone Thermostat User’s Manual for details.)

System Startup Checkout & Troubleshooting

The following is a summary of the sequence for typical fi rst 
operation to check out the system.  Reference is made to 
INSTALLER SETTINGS and SERVICE INFORMATION 
described above.

1. Install system hardware as described in the individual 

component installation instructions.

2.  Install power and control wiring to all system components, 

including the controller, in accordance with the iQ Field 
Wiring Installation Instructions.

3.  Perform pre-charge evacuation of fi eld-installed refrigerant 

lines as described in preceding sections.

4. For iQ Zone systems, fi rst apply 12 volt dc power to the 

zone control board with the provided AC/DC converter. Apply 
electrical power to the system (including the heat pump). 
The controller screen display backlight should come on, 
and the “iQ” splash screen should appear. If it does not, 
trace the 24 vac control power to the “R” terminal on the 
thermostat.  CONFIGURATION NEEDED should appear 
on the top line of the Main Screen (unless the thermostat 
had been previously used on a similar iQ system).

5.  Proceed with System Confi guration from the INSTALLER 

SETTINGS menu (described above). On the SYSTEM 
CONFIGURATION screen verify that the using size (2 ton, 
3 ton, or 4 ton) is correct as indicated. If the wrong value 
is shown, the inverter may require re-initialization. Contact 
the service representative of the distributor in this case.

 

On the same screen, the entries under COMMUNICATION 
should be followed by “OK”. If “CHECK” appears for a 
communication item, go to the COMMUNICATION STATUS 
screen (in the SERVICE INFORMATION menu, described 
above), and view which elements are not communicating.  
Trace and check the three communication wires throughout 
the system. If isolating a communication problem proves to 
be diffi cult, it may be useful to disconnect all communication 
wires except those which link the thermostat and the non-
communicating element.

6.  If COMMUNICATION STATUS was not checked during the 

previous step, check it at this time.  All listed items should 
show a status of “OK”. If any show “BAD”, determine the 
source of the problem as indicated in the previous step, 
and resolve.

7.  For iQ Zone systems only, the main screen should appear 

with no temperature reading, and “ZONE CTRL” should 
appear below “OFF”.  If this is not the case, go to the ZONE 
CONTROL screen from the SETTINGS menu, and change 
the zone control option to ENABLE.  If ZONE CONTROL 
does not show up on that menu, the iQ controller has never 
communicated with the zone control board, and power and 

communication wiring to the zone control board need to be 
checked.  If the main screen reverts to back to the zoning-
disabled screen (showing room temperature), power and 
communication wiring to the zone control board need to 
be checked.

8.  Set date and time as described above. This will provide a 

“time stamp” for any fault which may arise during system 
checkout.

9. If the installation includes a new gas furnace, check out 

its operation fi rst.  This may be best accomplished from 
FURNACE TESTS under SERVICE TESTS from the 
INSTALLER SETTINGS menu (see above).  Follow steps 
instructions provided in the furnace’s installation instructions.  
Be sure to verify blower operation during the test.

10. If the outdoor temperature is above 60°F (14°C), test the 

refrigerant system running in cooling mode fi rst.  If the 
outdoor temperature is between 12° and 60°F (-11 and 
14°C), test the refrigerant system running in heating mode 
fi rst.  This may best be accomplished from CHARGE MODE 
under SERVICE TESTS from the INSTALLER SETTINGS 
menu.  Follow the refrigerant charge adjustment procedure 
explained above. Note that if a fault is determined in the 
outdoor equipment, the backup heating means (electric 
strip heat or gas furnace) will start instead.

11. When charge adjustment is completed (if required), run 

the heat pump in both cooling and heating modes.  This 
may also be done using SERVICE TESTS although some 
diagnostic messages are disabled in that method.

12. Check the FAULT STATUS screen (described above) 

for any faults logged during the startup process.  Any 
message listed as “ACTIVE FAULT” refers to a condition 
which either still exists or occurred within the preceding 5 
minutes.  Every fault or notifi cation should appear in the 
FAULT HISTORY log which starts on the same screen.  
The last 10 faults to have occurred are retained in this 
list.  Each new item pushes other logged faults down in 
the list.  The second line associated with each of the 10 
entries includes the time and date of detection.  While 
the wording of fault messages is intended to provide a 
reasonable indication as to the responsible condition, the 
information conveyed by the abbreviated wording is limited.  
Consequently the installer should refer to training literature 
for further information in understanding fault messages.

13. If needed, make use of information provided below under 

Troubleshooting: What to Expect with Normal Operation.

14. Independently confi rm operation of any accessories 

installed with the heat pump system following instructions 
provided with that equipment.

15. Complete the remainder of confi guration settings and 

entries as specifi ed above under Installer Settings and 
Other Confi guration Entries.

16. For iQ Zone systems, confi rm the zone system setup by 

checking information on the ZONING DATA and ZONE 
MODULE STATUS screens, accessed from the SERVICE 
INFORMATION menu. (See SYSTEM DIAGNOSIS AND 
TROUBLESHOOTING below.).

Summary of Contents for iQDrive

Page 1: ...electronic air cleaners and U V ultraviolet sterilizing lamps Refer to the System Operation section below for a complete description of how to use the various features of the system In addition to pr...

Page 2: ...ORMATION Screens 10 Other Configuration Entries 11 Minimum Heat Pump Operating Temp 11 Auto Changeover Time 12 Date and Time 12 Program Schedule vs Nonprogrammable 12 Dehumidification 12 Humidity Sett...

Page 3: ...pment Consult local building codes for rooftop installations After a location has tentatively been selected trace routing of new or pre existing refrigerant lines two and power and control wiring See...

Page 4: ...lace the control panel cover before applying power IMPORTANT It is critical that the wires meant to connect to 24 vaccontrolpower RED GRAY arenotmistakenly connected to the communication bus wires YEL...

Page 5: ...frigerant gauge manifold to both the vapor and liquid service valves See Figure 8 Connect the center port to the vacuum pump 2 Open both manifold valves and start the vacuum pump After a short time it...

Page 6: ...ervice valve and suction service port located at the left side of the access panel above the liquid service valve See Figure 8 2 Start the system in CHARGE MODE HEATING Allow the system to run 15 minu...

Page 7: ...ew thermostat or moving a thermostat to a different type of iQ system The outdoor unit should be powered up when confirming or entering system configuration With the first line SYSTEM CONFIGURATION se...

Page 8: ...king changes or entries under ACCESSORIES is optional Dealer Information Usethe or keystoselectDEALERINFORMATION Press the key to enter the dealer information summary screen and submenus and screens T...

Page 9: ...der that the unit is operating in an abnormal service mode Select OFF from the list that includes ON and OFF and SAVE when finished FURNACE TESTS Runs the system at the selected fire level to allow co...

Page 10: ...MODEL NUMBER 20 2 tons 30 3 tons etc With correct configuration only 20 30 or 40 should appear here LOW PRESSURE SW shows the state of the low pressure switch Any COMPR ERROR CODE number normally 0 w...

Page 11: ...s helpful system status messages including whether or not the system is dehumidifying during cooling H E A T P U M P H E A T I N G U S E D D E M A N D S P 7 0 0 COMP RPM R O O M T E M P A C T S T E P...

Page 12: ...from having to do it but provides an accurate time and date stamp for any faults logged during installation checkout for example in FAULT HISTORY By default the clock is in 12 hour format This may be...

Page 13: ...The humidify setpoint can be set in the range 30 to 45 in increments of 5 The dehumidify setpoint can be set in the range 35 to 70 in increments of 5 Press the key to save any changes 5 Press the key...

Page 14: ...deliver air to all zones when not heating or cooling set the Fan Mode to ON The Intermittent Fan featuredescribedearlierwillalsooperate servingallzones Refer to the iQ Drive User s Manual for other de...

Page 15: ...u the iQ controller has never communicated with the zone control board and power and communication wiring to the zone control board need to be checked If the main screen reverts to back to the zoning...

Page 16: ...ELECTRIC SHOCK HAZARD Disconnect power before servicing the outdoor unit Failure to follow these instructions may result in electric shock or death Trouble shooting the outdoor unit may require that p...

Page 17: ...om the interface board Check for 24 vac between R and C on the interface board and check that the tabs marked R and C on the interface board are wired to R and C on the EXV board These should not be c...

Page 18: ...verse There is a configurable delay Auto Changeover Time between operating in heating and restarting in cooling or the reverse when in AUTO mode The default delay for this changeover is 60 minutes Abn...

Page 19: ...changes processed until zone dampers have completed any prior operation For example an extra minute delay is deliberately included when one or more zones are closed MAINTENANCE IMPORTANT Be certain t...

Page 20: ...20 Figure 3 iQ Drive Heat Pump Control Panel Inverter black plastic case Outdoor Interface Board Low Voltage Control Wiring Compartment Contactor Outdoor EXV Board...

Page 21: ...ER EXV REACTOR T2 T1 L1 L2 NO C A B CCH RELAY REVERSING VALVE COIL OUTDOOR AMBIENT TEMP SENSOR COMPR DISCHG TEMP SENSOR LOW PRESSURE SWITCH OD FAN MOTOR SUCTION LINE THERMISTOR 2X FIELD WIRING TO INDO...

Page 22: ...22 Figure 5 Low Voltage Compartment Control Wiring Connections GRN GND DX DX WHT YEL RED GRY C R Figure 6 iQ Heat Pump Control Wiring Outdoor Destinations...

Page 23: ...23 Figure 7 Wire Looping Through a Toroidial Choke SINGLE LOOP SHOWN Figure 8 Service Ports and Valves Below Control Panel Suction Service Port Vapor Line Service Valve Liquid Line Service Valve...

Page 24: ...efrigerantif above the curve AddRefrigerantif belowthe curve 3 Ton 2 Ton 4 Ton 240 260 280 300 320 340 360 380 75 80 85 90 95 100 105 110 115 Liquid Pressure psig Liquid Temperature F Heating Mode Out...

Page 25: ...HEAT PUMP USAGE LIMIT BACKUP HEAT RESPONSE OFFSETS INDOOR TEMPERATURE REMOTE INDOOR TEMP RELATIVE HUMIDITY HEAT ANTICIPATOR SCREEN SETTINGS FAHRENHEIT OR CELSIUS 12 OR 24 HOUR CLOCK CONTRAST INTERMITT...

Page 26: ...R PHONE SELECT BRAND NAME MODEL NUMBER CONTRACTOR NAME CONTRACTOR PHONE ACCESSORIES AIR FILTER HUMIDIFIER UV LAMP AIR CLEANER AIR FILTER CHANGE HUMIDIFIER CHANGE UV LAMP CHANGE AIR CLEANER CHANGE SERV...

Page 27: ...on Behind Interface Board to the left of blue DIP switch block Figure 13 Interface Board LED Locations Inverter LED to the left of blue DIP switch block Communication LED DEF CCH Y RV Figure 14 EXV Bo...

Page 28: ...NS WITH THE OWNER 708921 Specifications illustrations subject to change without notice or incurring obligations O Fallon MO Printed in U S A 09 10 Power Plug Red Power LED iQ Comm LED s Zone Network L...

Reviews: