Nordyne iQDrive Installation Instructions Manual Download Page 4

4

•  A properly sized branch circuit and disconnect switch must 

be installed where it is easily accessible and within line of 
sight of the outdoor unit.

•  Remove the control panel cover.  Route the power and ground 

wires (3 wires, including earth ground) from the disconnect 
box to the unit.  Use of outdoor shielded conduit (metal 
lined Sealtite

®

) is required. The electrical conduit opening 

is located on the lower left corner of the control box.

•  Connect the power wires to L1 and L2 box lugs of the 

contactor, and the ground wire to the grounding lug to the 
left of the contactor. See Figures 2 and 3. Only copper wires 
should be used.

•  Replace the control panel cover before applying power.

Control Circuit Wiring

The heat pump is designed to operate with a 24 VAC Class 
II control circuit. Control circuit wiring must comply with the 
latest version of the National Electrical Code (ANSI/NFPA 
70) as supplemented by local building codes.

In general, 24 VAC control power and communication bus 
wiring must be run to interconnect the thermostat/controller, 
the indoor unit, and the outdoor unit.  The “hub” of this network 
and source of the 24 VAC is located within the indoor unit (air 
handler or furnace).  Refer to iQ Drive System Field Wiring 
Instructions, NORDYNE document 709031 shipped with the 
controller, for connection of control wires to the indoor unit 
and for description of other indoor fi eld wiring, including to 
the controller.

Five (5) wires must be run between the indoor unit and the 
outdoor unit (2 for 24 VAC power and 3 for communications).  
Use one shielded cable (3 or more conductors) for 
communications only, and a separate cable or pair of wires 
for control power.  Refer to wiring diagram Figure 4 and Table 
II.

1.  Pass the 5 control wires into the hole in the lower right side 

of the control panel of the outdoor unit, into the separate 
low voltage wiring compartment. See Figures 5 and 6.

2. Locate the 5 corresponding factory-wired leads with 

stripped ends.  Assure that each of these 5 wires (on the 
factory wiring side of the wire connections) loops around 
and through the “donut” (toroidal choke).  Refer to Figure 
7 which shows one wire making a single loop.

3. Connect each of the 5 fi eld-run wires to its factory-wired 

counterpart using a wire nut, as indicated in Figures 4, 5 
and 6.

4.  Replace the control panel cover before applying power.

 IMPORTANT

It is critical that the wires meant to connect to 24 
vac control power (RED & GRAY) are not mistakenly 
connected to the communication bus wires (YEL, 
WHT, GRN). 24 volts applied to the communication 
bus will damage the equipment.

Communication Wiring

Indoor 

Interface 

Board 

Terminal

Indoor 

Interface 

Board plug 

wire color

Outdoor unit 

wire color

Outdoor Interface 

Board Terminal 

(RHS circuit 

board)

DX+

YEL

YEL

3 pin 3 wire white 
connector plug at 

RHS circuit board 

terminal

“INDOOR”

DX-

WHT

WHT

GND

GRN

GRN

Control Power Wiring

R (screw)

[no factory 

wire]

RED

“R” terminal screw

C (screw)

[no factory 

wire]

GRY

(contactor coil, 

RHS)

Table 2. Control Wiring to Outdoor iQ Heat Pump Unit

iQ Zone Control Wiring

For iQ Zone systems, fi eld wiring is required to connect the 
Airzone control board to the iQ communication bus and to 
provide a ground connection for the separate zoning control 
and communication network. Refer to the iQ Field Wiring 
Instruction document provided in the iQ controller kit for more 
details. A 3-wire cable must be run from a splice point in the 
iQ communication bus to the one 3-pin connector on the 
Airzone control board.

Recheck Wiring

Check that wire routing is correct and connections are secure 
for all power and control wiring.

REFRIGERANT LINE CONNECTIONS

Line Design and Routing

Refrigerant lines must be connected by a licensed EPA 
certifi ed technician following sound established installation 
practice. Once the heat pump location has been determined 
and the unit set in place the refrigerant lines should be routed 
and connected.

•  Refrigerant lines should follow a direct path from the indoor 

coil to the outdoor unit avoiding sharp bends.  When lines 
pass through walls, make sure to properly seal and support 
them so that vibration is not transmitted to the structure.

•  Refrigerant tubing should be supported in a manner which 

assures that the tubing will not vibrate or wear as a result 
of contact with sharp materials or edges during system 
operation.

•  Lines must be clean refrigeration-grade copper.
•  Avoid removing caps and plugs from the heat pump or lines 

until they are ready to be connected.

•  Insulate the vapor line with refrigerant line insulation ¼” wall 

thickness or greater.

Proper system performance and oil management depend on 
properly selecting the liquid and vapor line sizes. Refer to Table 
III for the proper size of fi eld supplied lines. The maximum 
allowable refrigerant line length is 100 ft.

Summary of Contents for iQDrive

Page 1: ...electronic air cleaners and U V ultraviolet sterilizing lamps Refer to the System Operation section below for a complete description of how to use the various features of the system In addition to pr...

Page 2: ...ORMATION Screens 10 Other Configuration Entries 11 Minimum Heat Pump Operating Temp 11 Auto Changeover Time 12 Date and Time 12 Program Schedule vs Nonprogrammable 12 Dehumidification 12 Humidity Sett...

Page 3: ...pment Consult local building codes for rooftop installations After a location has tentatively been selected trace routing of new or pre existing refrigerant lines two and power and control wiring See...

Page 4: ...lace the control panel cover before applying power IMPORTANT It is critical that the wires meant to connect to 24 vaccontrolpower RED GRAY arenotmistakenly connected to the communication bus wires YEL...

Page 5: ...frigerant gauge manifold to both the vapor and liquid service valves See Figure 8 Connect the center port to the vacuum pump 2 Open both manifold valves and start the vacuum pump After a short time it...

Page 6: ...ervice valve and suction service port located at the left side of the access panel above the liquid service valve See Figure 8 2 Start the system in CHARGE MODE HEATING Allow the system to run 15 minu...

Page 7: ...ew thermostat or moving a thermostat to a different type of iQ system The outdoor unit should be powered up when confirming or entering system configuration With the first line SYSTEM CONFIGURATION se...

Page 8: ...king changes or entries under ACCESSORIES is optional Dealer Information Usethe or keystoselectDEALERINFORMATION Press the key to enter the dealer information summary screen and submenus and screens T...

Page 9: ...der that the unit is operating in an abnormal service mode Select OFF from the list that includes ON and OFF and SAVE when finished FURNACE TESTS Runs the system at the selected fire level to allow co...

Page 10: ...MODEL NUMBER 20 2 tons 30 3 tons etc With correct configuration only 20 30 or 40 should appear here LOW PRESSURE SW shows the state of the low pressure switch Any COMPR ERROR CODE number normally 0 w...

Page 11: ...s helpful system status messages including whether or not the system is dehumidifying during cooling H E A T P U M P H E A T I N G U S E D D E M A N D S P 7 0 0 COMP RPM R O O M T E M P A C T S T E P...

Page 12: ...from having to do it but provides an accurate time and date stamp for any faults logged during installation checkout for example in FAULT HISTORY By default the clock is in 12 hour format This may be...

Page 13: ...The humidify setpoint can be set in the range 30 to 45 in increments of 5 The dehumidify setpoint can be set in the range 35 to 70 in increments of 5 Press the key to save any changes 5 Press the key...

Page 14: ...deliver air to all zones when not heating or cooling set the Fan Mode to ON The Intermittent Fan featuredescribedearlierwillalsooperate servingallzones Refer to the iQ Drive User s Manual for other de...

Page 15: ...u the iQ controller has never communicated with the zone control board and power and communication wiring to the zone control board need to be checked If the main screen reverts to back to the zoning...

Page 16: ...ELECTRIC SHOCK HAZARD Disconnect power before servicing the outdoor unit Failure to follow these instructions may result in electric shock or death Trouble shooting the outdoor unit may require that p...

Page 17: ...om the interface board Check for 24 vac between R and C on the interface board and check that the tabs marked R and C on the interface board are wired to R and C on the EXV board These should not be c...

Page 18: ...verse There is a configurable delay Auto Changeover Time between operating in heating and restarting in cooling or the reverse when in AUTO mode The default delay for this changeover is 60 minutes Abn...

Page 19: ...changes processed until zone dampers have completed any prior operation For example an extra minute delay is deliberately included when one or more zones are closed MAINTENANCE IMPORTANT Be certain t...

Page 20: ...20 Figure 3 iQ Drive Heat Pump Control Panel Inverter black plastic case Outdoor Interface Board Low Voltage Control Wiring Compartment Contactor Outdoor EXV Board...

Page 21: ...ER EXV REACTOR T2 T1 L1 L2 NO C A B CCH RELAY REVERSING VALVE COIL OUTDOOR AMBIENT TEMP SENSOR COMPR DISCHG TEMP SENSOR LOW PRESSURE SWITCH OD FAN MOTOR SUCTION LINE THERMISTOR 2X FIELD WIRING TO INDO...

Page 22: ...22 Figure 5 Low Voltage Compartment Control Wiring Connections GRN GND DX DX WHT YEL RED GRY C R Figure 6 iQ Heat Pump Control Wiring Outdoor Destinations...

Page 23: ...23 Figure 7 Wire Looping Through a Toroidial Choke SINGLE LOOP SHOWN Figure 8 Service Ports and Valves Below Control Panel Suction Service Port Vapor Line Service Valve Liquid Line Service Valve...

Page 24: ...efrigerantif above the curve AddRefrigerantif belowthe curve 3 Ton 2 Ton 4 Ton 240 260 280 300 320 340 360 380 75 80 85 90 95 100 105 110 115 Liquid Pressure psig Liquid Temperature F Heating Mode Out...

Page 25: ...HEAT PUMP USAGE LIMIT BACKUP HEAT RESPONSE OFFSETS INDOOR TEMPERATURE REMOTE INDOOR TEMP RELATIVE HUMIDITY HEAT ANTICIPATOR SCREEN SETTINGS FAHRENHEIT OR CELSIUS 12 OR 24 HOUR CLOCK CONTRAST INTERMITT...

Page 26: ...R PHONE SELECT BRAND NAME MODEL NUMBER CONTRACTOR NAME CONTRACTOR PHONE ACCESSORIES AIR FILTER HUMIDIFIER UV LAMP AIR CLEANER AIR FILTER CHANGE HUMIDIFIER CHANGE UV LAMP CHANGE AIR CLEANER CHANGE SERV...

Page 27: ...on Behind Interface Board to the left of blue DIP switch block Figure 13 Interface Board LED Locations Inverter LED to the left of blue DIP switch block Communication LED DEF CCH Y RV Figure 14 EXV Bo...

Page 28: ...NS WITH THE OWNER 708921 Specifications illustrations subject to change without notice or incurring obligations O Fallon MO Printed in U S A 09 10 Power Plug Red Power LED iQ Comm LED s Zone Network L...

Reviews: