Nordyne iQDrive Installation Instructions Manual Download Page 12

12

economical to run the backup heat rather than the heat pump.  
The default and minimum value for this parameter is 12°F.  Once 
the outdoor temperature rises above this setpoint, the heat 
pump will be permitted to operate again after the demand has 
been satisfi ed and backup heat has shut off. (Determination 
of the balance point is not simple and depends on a variety of 
local factors, including the price of electricity and gas at any 
particular time.)

 

To modify the value, perform the following:

1. From the Main Screen, press the   or   key to select 

MENU at the bottom of the screen, then press the   key 
to see the Main Menu.

2. Use the   or   key to select SETTINGS, then press the 

 key to enter the Settings menu.

3. Use the   or   key to select OPTIONS, then press the   

key to enter the Options screen.

O P T I O N S

P R O G R A M   S C H E D   U S A G E

6 0

O N

4   S C H E D   E V E N T S / D A Y

D E H U M I D I F I C A T I O N

A U T O   C H A N G E O V E R   T I M E

S M A R T   R E C O V E R Y

O F F

H E A T   P U M P   U S A G E   L I M I T







M I N U T E S

N O T   B E L O W

1 4 F

4. Use the   or   key to select the value under HEAT PUMP 

USAGE LIMIT, then press the   key to allow changing the 
setting.

5. Use the   or   key to change the value (2°F increments), 

then press the   key to save the setting.

6. Press the   key multiple times to return to the Main Screen.

Auto Changeover Time

This adjustment enables AUTO mode, which allows the system 
to automatically switch between heating and cooling without 
having to touch the controller. Autochangeover time is the delay 
(minimum time) between the end of cooling operation and 
the beginning of heating operation (or the reverse). DISABLE 
removes AUTO as an available mode. Otherwise, the time may 
be selected from 15 to 120 minutes (default 60 minutes).To 
modify the value, perform the following:

1. From the Main Screen, press the   or   key to select 

MENU at the bottom of the screen, then press the   key 
to see the Main Menu.

2. Use the   or   key to select SETTINGS, then press the 

 key to enter the Settings menu.

3. Use the   or   key to select OPTIONS, then press the   

key to enter the Options screen.

4. Use the 

 or   key to select the value under AUTO 

CHANGEOVER TIME, then press the   key to allow 
changing the setting.

5. Use the   or   key to change the value, then press the   

key to save the setting.

6. Press the   key multiple times to return to the Main Screen.

Date and Time

Setting date and time early in the installation process not only 
saves the homeowner from having to do it, but provides an 
accurate time and date stamp for any faults logged (during 
installation checkout, for example) in FAULT HISTORY.  By 
default, the clock is in 12 hour format.  This may be changed 
on the OPTIONS menu screen (see either of the above two 
items). Daylight Saving Time is automatically taken into account 
but may be disabled from the SET DATE AND TIME menu 
screen.

 

To set date and time, perform the following:

1. From the Main Screen, press the   or   key to select 

MENU at the bottom of the screen, then press the   key 
to see the Main Menu.

2.  SET DATE AND TIME will be selected.  Press the   key 

two times.

3. Enter the year, month, day (date), hour, and minute on 

consecutive screens.  Use the   or   key to change any 
value, and press the   key to advance to the next.  After 
setting the minutes value, press the   key to save the 
complete setting.

4. Press the   key multiple times to return to the Main Screen.

Program Schedule versus Nonprogrammable.

While using “setback” program schedules are advisable to 
take advantage of potential economic and energy savings, 
some homeowners still prefer to perform setpoint adjustment 
by exclusively using the   and   keys.  The following setting 
provides the nonprogrammable option or the option for different 
numbers of events per day (2 or 4) on the program schedule. 
To set the program schedule option, perform the following:

1. From the Main Screen, press the   or   key to select 

MENU at the bottom of the screen, then press the   key 
to see the Main Menu.

2. Use the   or   key to select SETTINGS, then press the 

 key to enter the Settings menu.

3. Use the   or   key to select OPTIONS, then press the   

key to enter the Options screen.

4. The value under PROGRAM SCHED USAGE will be 

selected.  Press the   key to allow changing the setting.

5. Use the   or   key to change the value between “NON 

PROGRAMMABLE”, “4 SCHED EVENTS/DAY”, “2 SCHED 
EVENTS/DAY”, and “2 EVENTS/D BUSINESS”.  Then press 
the   key to save the setting.  (The difference between “2 
EVENTS/D BUSINESS” and “2 SCHED EVENTS/DAY” 
is only the name given to the time blocks within a daily 
schedule.)

6. Press the   key multiple times to return to the Main Screen.

Dehumidifi cation

When dehumidifi cation is enabled (as it is by default), 
the system will (depending upon the conditions) suspend 
responding to room temperature and lower blower speed to 
enhance removal of moisture from the air circulating through 
the indoor coil.  When operating in this manner, the unit will 
run cycles of 10 minutes dehumidifying, 5 minutes normal 
cooling (adjusting capacity). See also setting the humidity 
setpoints in (6) below. To change the dehumidifi cation option, 
perform the following:

Summary of Contents for iQDrive

Page 1: ...electronic air cleaners and U V ultraviolet sterilizing lamps Refer to the System Operation section below for a complete description of how to use the various features of the system In addition to pr...

Page 2: ...ORMATION Screens 10 Other Configuration Entries 11 Minimum Heat Pump Operating Temp 11 Auto Changeover Time 12 Date and Time 12 Program Schedule vs Nonprogrammable 12 Dehumidification 12 Humidity Sett...

Page 3: ...pment Consult local building codes for rooftop installations After a location has tentatively been selected trace routing of new or pre existing refrigerant lines two and power and control wiring See...

Page 4: ...lace the control panel cover before applying power IMPORTANT It is critical that the wires meant to connect to 24 vaccontrolpower RED GRAY arenotmistakenly connected to the communication bus wires YEL...

Page 5: ...frigerant gauge manifold to both the vapor and liquid service valves See Figure 8 Connect the center port to the vacuum pump 2 Open both manifold valves and start the vacuum pump After a short time it...

Page 6: ...ervice valve and suction service port located at the left side of the access panel above the liquid service valve See Figure 8 2 Start the system in CHARGE MODE HEATING Allow the system to run 15 minu...

Page 7: ...ew thermostat or moving a thermostat to a different type of iQ system The outdoor unit should be powered up when confirming or entering system configuration With the first line SYSTEM CONFIGURATION se...

Page 8: ...king changes or entries under ACCESSORIES is optional Dealer Information Usethe or keystoselectDEALERINFORMATION Press the key to enter the dealer information summary screen and submenus and screens T...

Page 9: ...der that the unit is operating in an abnormal service mode Select OFF from the list that includes ON and OFF and SAVE when finished FURNACE TESTS Runs the system at the selected fire level to allow co...

Page 10: ...MODEL NUMBER 20 2 tons 30 3 tons etc With correct configuration only 20 30 or 40 should appear here LOW PRESSURE SW shows the state of the low pressure switch Any COMPR ERROR CODE number normally 0 w...

Page 11: ...s helpful system status messages including whether or not the system is dehumidifying during cooling H E A T P U M P H E A T I N G U S E D D E M A N D S P 7 0 0 COMP RPM R O O M T E M P A C T S T E P...

Page 12: ...from having to do it but provides an accurate time and date stamp for any faults logged during installation checkout for example in FAULT HISTORY By default the clock is in 12 hour format This may be...

Page 13: ...The humidify setpoint can be set in the range 30 to 45 in increments of 5 The dehumidify setpoint can be set in the range 35 to 70 in increments of 5 Press the key to save any changes 5 Press the key...

Page 14: ...deliver air to all zones when not heating or cooling set the Fan Mode to ON The Intermittent Fan featuredescribedearlierwillalsooperate servingallzones Refer to the iQ Drive User s Manual for other de...

Page 15: ...u the iQ controller has never communicated with the zone control board and power and communication wiring to the zone control board need to be checked If the main screen reverts to back to the zoning...

Page 16: ...ELECTRIC SHOCK HAZARD Disconnect power before servicing the outdoor unit Failure to follow these instructions may result in electric shock or death Trouble shooting the outdoor unit may require that p...

Page 17: ...om the interface board Check for 24 vac between R and C on the interface board and check that the tabs marked R and C on the interface board are wired to R and C on the EXV board These should not be c...

Page 18: ...verse There is a configurable delay Auto Changeover Time between operating in heating and restarting in cooling or the reverse when in AUTO mode The default delay for this changeover is 60 minutes Abn...

Page 19: ...changes processed until zone dampers have completed any prior operation For example an extra minute delay is deliberately included when one or more zones are closed MAINTENANCE IMPORTANT Be certain t...

Page 20: ...20 Figure 3 iQ Drive Heat Pump Control Panel Inverter black plastic case Outdoor Interface Board Low Voltage Control Wiring Compartment Contactor Outdoor EXV Board...

Page 21: ...ER EXV REACTOR T2 T1 L1 L2 NO C A B CCH RELAY REVERSING VALVE COIL OUTDOOR AMBIENT TEMP SENSOR COMPR DISCHG TEMP SENSOR LOW PRESSURE SWITCH OD FAN MOTOR SUCTION LINE THERMISTOR 2X FIELD WIRING TO INDO...

Page 22: ...22 Figure 5 Low Voltage Compartment Control Wiring Connections GRN GND DX DX WHT YEL RED GRY C R Figure 6 iQ Heat Pump Control Wiring Outdoor Destinations...

Page 23: ...23 Figure 7 Wire Looping Through a Toroidial Choke SINGLE LOOP SHOWN Figure 8 Service Ports and Valves Below Control Panel Suction Service Port Vapor Line Service Valve Liquid Line Service Valve...

Page 24: ...efrigerantif above the curve AddRefrigerantif belowthe curve 3 Ton 2 Ton 4 Ton 240 260 280 300 320 340 360 380 75 80 85 90 95 100 105 110 115 Liquid Pressure psig Liquid Temperature F Heating Mode Out...

Page 25: ...HEAT PUMP USAGE LIMIT BACKUP HEAT RESPONSE OFFSETS INDOOR TEMPERATURE REMOTE INDOOR TEMP RELATIVE HUMIDITY HEAT ANTICIPATOR SCREEN SETTINGS FAHRENHEIT OR CELSIUS 12 OR 24 HOUR CLOCK CONTRAST INTERMITT...

Page 26: ...R PHONE SELECT BRAND NAME MODEL NUMBER CONTRACTOR NAME CONTRACTOR PHONE ACCESSORIES AIR FILTER HUMIDIFIER UV LAMP AIR CLEANER AIR FILTER CHANGE HUMIDIFIER CHANGE UV LAMP CHANGE AIR CLEANER CHANGE SERV...

Page 27: ...on Behind Interface Board to the left of blue DIP switch block Figure 13 Interface Board LED Locations Inverter LED to the left of blue DIP switch block Communication LED DEF CCH Y RV Figure 14 EXV Bo...

Page 28: ...NS WITH THE OWNER 708921 Specifications illustrations subject to change without notice or incurring obligations O Fallon MO Printed in U S A 09 10 Power Plug Red Power LED iQ Comm LED s Zone Network L...

Reviews: