Replacing the Battery
Follow these steps to replace the battery:
1. Remove the flat-head screws to extract the PICO controller from the electrical cabinet; detach cables.
2. Release the four M3 outer hexagon screws from the front panel.
3. Carefully pull the front plate out approximately 5 cm by the handle, taking care not to pull or
stretch the internal cables.
4. Place the PICO controller on its side such that the circuit board with the battery is on the
bottom.
NOTE:
If needed for space, the plug connection between the front and the side (lower) circuit
board can be removed.
5. Use a suitable tool (e.g., a screwdriver) to extract the battery from under the bracket.
6. Insert a new battery.
7. Reassemble the unit in reverse order.
8. When the controller is switched back on, “Check battery” will be displayed because the internal time and
date have been erased. Enter the current time and date to prevent the “Check Battery” message from being
displayed whenever the controller is switched on.
Replacement Parts
Part #
Description
7027455
Cable, power, 24V, 2.0 m (PICO controller power supply cable)
7028222
Cable, PICO controller /
Toµch
controller / PLC, 1.0 + 2.0 m-ADSIG (Y-cable)
NOTE:
This cable is ordered separately.
Part Numbers
Part #
Description
7029238
PICO Controller 2+2-XCH-V3, 2 channel
7029242
PICO Controller 2+2-XCH-V3, 4 channel
PICO Controller 2+2-XCH-V3