CAN Communication Command Examples (continued)
WRITE Command Examples
1FF 28
10 01 01
40
D0 00 00 Request: WRITE Ch1; Line 01, Pulse Time=6.50 (IEE754). Set LS=0 and TAN=1.
5FF 28
10 01 01
40
D0 00 00 Response: Error Bit 0. No error.
1FF 28
20 01 16
41
18 00 00 Request: WRITE Ch1; Line 01, Cycle=9.50 (IEE754). LS=0. TAN=2.
5FF 28
20 01 16
41
18 00 00 Response: Error Bit 0. No error.
1FF 28
30 64 0D 42
0C 00 00 Request: WRITE Ch1; Line 100, Temperature=35.0 (IEE754). LS=0. TAN=3.
5FF 28
30 64 0D 42
0C 00 00 Response: Error Bit 0. No error.
1FF 28
40 01 03
00
00 00 06 Request: WRITE Ch1; Line 01, Cycl.Count=6. LS=0 and TAN=4.
5FF 28
40 01 03
00
00 00 06 Response: Error Bit 0. No error.
1FF 22
50 63 05
00
00 00 32 Request: WRITE Ch3; Line 99, Linkage=50. LS=0 and TAN=5.
5FF 22
50 63 05
00
00 00 32 Response: Error Bit 0. No error.
1FF 21
60 0A 07
00
00 00 1A Request: WRITE Ch4; Line 10, Block Count=26. LS=0.TAN=6.
5FF 21
60 0A 07
00
00 00 1A Response: Error Bit 0. No error.
1FF 2F
70 64 0E
00
00 00 02 Request: WRITE Ch1+2+3+4; Line 100, Stop=2. LS=0.TAN=7.
5FF 2F
70 64 0E
00
00 00 02 Response: Error Bit 0. No error.
1FF 2C
80 64 0A 44
7A 00 00 Request: WRITE Ch1+2; Line 100, Container=1000.00 (IEE754). LS=0. TAN=8.
5FF 2C
80 64 0A 44
7A 00 00 Response: Error Bit 0. No error.
1FF 23
90 64 0B 42
C8 00 00 Request: WRITE Ch3+4; Line 100, Limit=100.00 (IEE754). LS=0. TAN=9.
5FF 23
90 64 0B 42
C8 00 00 Response: Error Bit 0. No error.
READ Command Examples
1FF 18
A0 01 01
xx
xx xx xx Request: READ Ch1; Line 01, Value for Pulse Time. LS=0. TAN=10.
5FF 18
A0 01 01
40
D0 00 00 Response with Value for Pulse Time=6.50. (IEE754). Error Bit 0. No error.
1FF 18
B0 01 16
xx
xx xx xx Request: READ Ch1; Line 01, Value for Cycle. LS=0. TAN=11.
5FF 18
B0 01 16
41
18 00 00 Response with Value for Cycle=9.50. (IEE754). Error Bit 0. No error.
1FF 18
C0 64 0D xx
xx xx xx Request: READ Ch1; Line 100, Value for Temperature. LS=0. TAN=12.
5FF 18
C0 64 0D 42
0C 00 00 Response with Value for Temperature=35.0. (IEE754). Error Bit 0. No error.
1FF 14
D0 01 03
xx
xx xx xx Request: READ Ch2; Line 01, Value for Cycl.count. LS=0. TAN=13.
5FF 14
D0 01 03
00
00 00 06 Response with Value for Cycl.count=6. Error Bit 0. No error.
1FF 12
E0 63 05
xx
xx xx xx Request: READ Ch3; Line 99, Value for Linkage. LS=0. TAN=14.
5FF 12
E0 63 05
00
00 00 32 Response with Value for Linkage=50. Error Bit 0. No error.
1FF 11
F0 0A 07
xx
xx xx xx Request: READ Ch4; Line 10, Value for Block Count. LS=0. TAN=15.
5FF 11
F0 0A 07
00
00 00 1A Response with Value for Block Count=26. Error Bit 0. No error.
PICO Controller 2+2-XCH-V3
25