54
Control voltage supply
CAUTION!
– Before connecting, ensure that the mains voltage corresponds with
the
control voltage of the unit (230 V/1 50…60 Hz).
– The humidifier must only be connected to a
mains supply with a
protective conductor
.
The connection to the control voltage is made in accordance with the wir
ing diagram, to the
terminal block “XE3”
in the control compartment. The
customer is to install a
service switch “Q6”
(all pole disconnecting device
with a minimum contact opening of 3 mm) and a
“F6”
fuse
(max. 10 A slow
acting)
in the supply line (these are both essential requirements).
The crosssection of the mains cable must comply with the applicable local
regulations (minimum of 1.5 mm
2
).
External safety circuit
To guarantee the safety of the humidification system, monitoring the opera
tion by means of a safety circuit is an absolute requirement.
To accomplish this, the
potential-free contacts (max. contact loading
250V/5A)
of external moni t or ing devices (e.g. safety high limit humidistat,
airflow monitor, ventilation interlock, etc.) are
connected in series to the
contacts “SC1” and “SC2” of the terminal block “XE2”
in accordance
with the wiring diagram.
DANGER!
Danger of electric hazard!
Mains voltage is connected to terminal block “XE2” (up to 240 V). The
steam humidifier must therefore be isolated from the mains supply (heat
ing and control voltage), before starting the connection work.
If, for whatever reason, no external monitoring devices are connected, a
connecting bridge “J” must be installed on the contacts “SC1” and “SC2” of
the terminal block “XE2”.
Do not apply any
extraneous voltage
to the terminals.
The crosssection of the cable must comply with the applicable local regula
tions (minimum of 1 mm
2
).