Heating voltage supply
CAUTION!
Before connecting, ensure that the mains voltage corresponds with the
heating voltage for the unit
(see type plate).
The connection to the heating voltage is made in accordance with the wir
ing diagram, to the
terminal block “XE1”
in the control compartment. The
customer is to install a
service switch “Q5”
(disconnecting device with a
minimum contact opening of 3 mm is an essential requirement) and a
fuse
group
“F5”
(essential requirement, fuses are to be as detailed in the fol
lowing table) in the supply line. The supply wiring is to be fed into the unit
via the clamp strap on the bottom of the unit.
Note
: Double units have separate heating voltage supplies for each cylinder.
Heating voltage
Max. steam
capacity
[kg/h]
Nordmann
AT4 ..
Nominal power
[kW]
Nominal
current
[A]
Main fuses F5
[A]
400V3
(400 V/3~/50...60 Hz)
5
534
3.8
5.4
3x 10
8
834
6.0
8.7
3x 16
15
1534
11.3
16.2
3x 25
23
2364
17.3
24.9
3x 35
32
3264
24.0
34.6
3x 50
45
4564
33.8
48.7
3x 80
64
6464
2x 24.0
2x 34.6
2x (3x 50)
65
6564
48.8
70.4
3x 100
90
9064
2x 33.8
2x 48.7
2x (3x 80)
130
13064
2x 48.8
2x 70.4
2x (3x100)
400V2
(400 V/2~/50...60 Hz)
5
524
3.8
9.4
3x 16
8
824
6.0
15.0
3x 25
230V3
(230 V/3~/50...60 Hz)
5
532
3.8
9.4
3x 20
8
832
6.0
15.1
3x 25
15
1532
11.3
28.2
3x 40
23
2362
17.3
43.3
3x 63
32
3262
24.0
60.2
3x 100
46
4662
2x 17.3
2x 43.3
2x (3x 63)
64
6462
2x 24.0
2x 60.2
2x (3x 100)
230V1
(230V/1~/50...60Hz)
5
522
3.8
16.3
25
8
822
6.0
26.1
40
The crosssection of the mains cable must comply with the applicable local
regulations.