19
3.7.2
Accessory details
3.7.2.1 Steam distribution pipe DV41-.../DV71-...
The steam distribution pipes are selected on the basis of the
duct width
(for horizontal installation) or the
duct height
(for vertical installation) and
the
capacity of the steam humidifier
.
Important!
Always select the longest possible steam distribution pipe (opti
mum humidification distance).
Steam distribution pipes for
Nordmann AT4
1)
Length (L) steam
distribution pipe
Duct width (B)
Type DV41-..
Type DV71-..
in mm
2)
in mm
41200
200
210...400
41350
71350
350
400...600
41500
71500
500
550...750
41650
71650
650
700...900
41800
71800
800
900...1100
411000
711000
1000
1100...1300
411200
711200
1200
1300...1600
711500
1500
1600...2000
711800
1800
2000...2400
712000
2000
2200...2600
712300
2300
2500...2900
712500
2500
2700...3100
1)
Material: CrNi steel
2)
special length on request
Note
: If the humidification distance (see chapter 5.4.2) has to be reduced for
technical reasons, the amount of steam per unit must be divided between
several steam distribution pipes
or the
steam distribution system Mul-
tiPipe
must be used. If this is the case, contact your Nordmann supplier.