Connection of the remote terminal (Option RP)
The optional remote terminal is to be connected via a fourwire cable to the
corresponding contacts of terminal block X15 on the power board of one
of the humidifiers.
Addtional humidifiers (max. 8) to be remote controlled are connected in
series via the contacts “D+” und “D–” of terminal block X15 to the humidifier
connected to the remote terminal using a twowire cable.
The maximun cable length between the units is 50 m. Cable section 0.5 mm
2
.
The termination of the remote terminal bus is established via the jumpers
JP1, JP4 and JP5 on the power boards of the remote terminal and the con
nected humidifiers (see table below).
Jumper settings for operation with optional remote terminal
Jumper
Function
Remote terminal
Unit(s)
in between
Last unit in
the chain
JP1
120Ω end resistor
X
X
JP4
Pull up resistor
X
JP5
Pull down resistor
X
LINK UP
EXTERNAL
CON.
CURRENT SENSOR
F4
315mAT
from contactor
to cylinder
AT4
ext.
REMOTE
D+ D– GND 5V 24V
X15
Unit 2
Unit 3
Last Unit
D+ D–GND 5V 24V
X15
D+ D–GND 5V 24V
X15
D+ D–GND 5V 24V
X15
JP1 JP4 JP5
JP1 JP4 JP5
JP1 JP4 JP5
Remote Terminal
D+ D–GND 5V 24V
X15
JP1 JP4 JP5
JP1 JP4 JP5