37
before diffuser
before/after filter/register
before/after fan, zone exit
* 2,5 x B
N
before aerosol filter
Installation notes and dimensions
The steam distribution pipes are designed for either
horizontal
installation
(on the duct wall) or, with accessories, for
vertical
installation (in the duct
floor). The
outlet orifices should always point upwards and at right
angles to the airflow
.
If possible, the steam distribution pipes should be installed on the
pressure
side
of the duct (
max. duct pressure 1500 Pa
). If the steam distribution
pipes are installed on the suction side of the duct, the
maximum vacuum
must not exceed 800 Pa
.
Select a location for the installation, tailored to suit your duct (see the fol
lowing illustrations) and position the steam distribution pipes in the duct so
that a uniform distribution of steam is achieved.
before control sensor
+
1.5 x B
N *
50 mm
50 mm
1 x B
N
1 x B
N
1 x B
N
5 x B
N
Summary of Contents for AT4 13064
Page 2: ......
Page 64: ...64 Notes...
Page 65: ...65 Notes...
Page 66: ...Notes...
Page 67: ...Nordmann Engineering Ltd Printed in Switzerland Technical modifications reserved...