20
3.7.2.2 MultiPipe steam distribution system
H
B
The
MultiPipe
steam distribution system is used in ventilation ducts with a
short humidification distance (for the calculation of the humidification dis
tance refer to chapter 5.4.2). When ordering an
MultiPipe
system the duct
dimension must be specified. Please consult the data in the following table.
MultiPipe
Number of steam
connectors
Max. steam
capacity
in kg/h
1)
Duct dimensions
Width B
in mm
Height H
in mm
System 1
1
32 (23)
4501500 4501650
System 2
2
65 (45)
4502200 4502200
System 4
4
130 (90)
4502500 8003200
1)
For duct widths <600 mm the value in brackets apply