NORDAC LINK (SK 250E-FDS ... SK 280E-FDS) – Users Manual for Frequency Inverters as Field Distributors
172
BU 0250 en-3021
C008
8.0
Parameter loss
Warning:
One of the cyclically saved messages such
as
operating hours
or
enabling time
could not be
saved successfully.
The warning disappears as soon as saving can be
successfully performed.
Pos: 604 /Anleitungen/Elektronik/FU und Starter/6. Meldungen zum Betriebszustand/Störmeldungen (Auflistung)/Warnung C012 [SK 180E ... SK 2xxE] @ 2\mod_1347457201968_388.docx @ 47274 @ @ 1
C012
12.1
Limit moto./Customer
"Drive switch
-
off limit"
Warning: 80 % of the drive switch-off limit (P534 [-01]) has
been exceeded.
•
Reduce load on motor
•
Set higher value in (P534 [-01]).
12.2
Limit gen.
"Generator switch
-
off limit"
Warning: 80 % of the generator switch-off limit (P534 [-02])
has been reached.
•
Reduce load on motor
•
Set higher value in (P534 [-02]).
12.3
Torque limit
Warning: 80 % of the limit from the potentiometer or the
setpoint source has been reached. P400 = 12
12.4
Current limit
Warning: 80 % of the limit from the potentiometer or the
setpoint source has been reached. P400 = 14
12.5
Load monitor
Warning due to overshooting or undershooting of
permissible load torques ((P525) … (P529)) for the time set
in (P528).
•
Adjust load.
•
Change limit values ((P525) ... (P527)).
•
Increase delay time (P528).