P523
Factory setting
(Factory setting)
0 … 3
{ 0 }
With the selection of the relevant value and confirmation via the ENTER key, the selected
parameter range is set to factory setting. Once this setting is made, the parameter value
automatically changes back to 0.
0 = No change:
Does not change the parameterisation.
1 = Load factory setting:
The complete parameterisation of the FI reverts to the factory
setting. All originally parameterised data are lost.
2 = Factory setting without bus:
All parameters of the frequency inverter, with the
exception of the bus parameters, are reset to the factory setting.
3 = Factory setting without motor data:
All parameters of the frequency inverter, with the
exception of the motor data parameters (
P201
to
P209
), are reset to the factory setting.
Pos: 442 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P500-P599/Parameter P523 und P420 – Werkseinstellung_Ergänzung [SK 2xxE-FDS] @ 12\mod_1467290502800_388.docx @ 335445 @ @ 1
Note:
The default values of parameter P420 [-05], [-06] and [-07] depend on the control elements
on option slots
H1
and
H2
.
Pos: 443 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P500-P599/Parameter P525 – Lastüberwachung Maximalwert @ 0\mod_1328093087228_388.docx @ 11433 @ @ 1
P525
[-01]
...
[-03]
Load control max
(Load monitoring maximum value)
S
P
1 ... 400 % / 401
{ all 401 }
Selection of up to 3 auxiliary values:
[-01] = Auxiliary value 1
[-02] = Auxiliary value 2
[-03] = Auxiliary value 3
Maximum load torque value.
Setting of the upper limit of load monitoring. Up to 3 values can be specified. Prefixes are not
taken into account, only the integer values are processed (motor / generator torque, right/left
rotation). The array elements [-01], [-02] and [-03] of parameters (P525) … (P527), or the entries
which are made there always belong together.
401 = OFF
Means that the function is switched off. No monitoring is performed. This is also the
basic setting for the FI.
Pos: 444 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P500-P599/Parameter P526 – Lastüberwachung Minimalwert @ 0\mod_1328093137197_388.docx @ 11456 @ @ 1
P526
[-01]
...
[-03]
Load control min
(Load monitoring, minimum value)
S
P
0 ... 400 %
{ all 0 }
Selection of up to 3 auxiliary values:
[-01] = Auxiliary value 1
[-02] = Auxiliary value 2
[-03] = Auxiliary value 3
Minimum load torque.
Setting of the lower limit value of load monitoring. Up to 3 values can be specified. Prefixes are
not taken into account, only the integer values are processed (motor / generator torque, right/left
rotation). The array elements [-01], [-02] and [-03] of parameters (P525) … (P527), or the entries
which are made there always belong together.
0 = OFF
Means that the function is switched off. No monitoring is performed. This is also the
basic setting for the FI.