5 Parameter
BU 0250 en-3021
145
Pos: 461 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P500-P599/Parameter P543 – Bus-Istwert 1-3 [SK 1x0E, SK 2xxE, SK 2xxE-FDS] @ 2\mod_1346932171510_388.docx @ 43296 @ @ 1
P543
[-01]
...
[-03]
Actual bus value 1 … 3
(Actual bus value 1 ...
3)
S
P
0 ... 57
{ [-01] = 1 }
{ [-02] = 4 }
{ [-03] = 9 }
The return status value can be selected for bus actuation in this parameter.
NOTE:
For further details, please refer to the relevant bus manual or the description for
(P418).
(Values from 0% … 100% correspond to 0000
hex
…
4000
hex
)
For standardisation of the actual values: (chapter 8.8).
[-01] = Actual bus value 1
[-02] = Actual bus value 2
[-03] = Actual bus value 3
(Definition of frequencies (chapter 8.9))
Pos: 462 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P500-P599/Parameter P543 – Bus-Istwert 1-3_Einstellungen [SK 2xxE-FDS] @ 12\mod_1467292402908_388.docx @ 335550 @ @ 1
0 =
Off
19 =
Setpoint frequency master value (
P503
)
1 =
Actual frequency
20 =
Target frequency aft. mast. val. ramp,
"Setpoint frequency after master value
ramp"
2 =
Actual speed
3 =
Current
21 =
Actual freq. without slip Master value
"Actual frequency without master value
slip"
4 =
Torque current (100% =
P112
)
5 =
Digital IO* status
22 =
Speed encoder,
"Speed from encoder"
6 =
8 =
Setpoint frequency
23 =
Actual frequency with slip
"Actual frequency with slip"
9 =
Error number
10 =
24 =
Master value
Actual freq.
w. slip
"Master value, actual freq. with slip"
12 =
BusIO Out Bits 0-7
13 =
53 =
Actual value 1 PLC
17 =
Value analog input 1
54 =
Actual value 2 PLC
18 =
Value of analog input 2,
55 =
Actual value 3 PLC
56 =
Actual value 4 PLC
57 =
Actual value 5 PLC
* assignment of the digital inputs for P543 = 5
Bit 0 = DIN 1 (FI)
Bit 1 = DIN 2 (FI)
Bit 2 = DIN 3 (FI)
Bit 3 = DIN 4 (FI)
Bit 4 = DIN 5 (FI)
Bit 5 = DIN 6 (FI)
Bit 6 = DIN 7 (FI)
Bit 7 = PTC input [FI]
Bit 8 = DI1, 1. SK…IOE
Bit 9 = DI2, 1. SK…IOE
Bit 10 = DI3, 1. SK…IOE
Bit 11 = DI4, 1. SK…IOE
Bit 12 = DOUT 1 (FI)
Bit 13 = mech. Brake (FI)
Bit 14 = DOUT 2 (FI)
Bit 15 = reserved
Pos: 463 /Allgemein/Allgemeingültige Module/---------Seitenumbruch kompakt --------- @ 13\mod_1476369695906_0.docx @ 2265495 @ @ 1
Summary of Contents for NORDAC LINK SK250E-FDS
Page 211: ...Key word index BU 0250 en 3021 211...
Page 212: ...6072502 3021...